Technical data

Configuration software for SINAUT ST7
1.12 Change matrix
Software
170 System Manual, 07/2009, C79000-G8976-C222-07
Object affected Operator activity in the
SINAUT configuration tool
Necessary follow-up action
Network nodes Deleting a network node All SINAUT connections running over this network node are
then invalid and are removed the next time you open the
SINAUT connection configuration. When necessary, these must
be replaced by alternative connections. The SDBs or DBs of all
modules that were involved in these deleted connections must
be regenerated in the subscriber administration.
Network nodes Canceling the networking of a
network node
All SINAUT connections running over this network node are
then invalid and are removed the next time you open the
SINAUT connection configuration. When necessary, these must
be replaced by alternative connections. The SDBs or DBs of all
modules that were involved in these deleted connections must
be regenerated in the subscriber administration.
SINAUT connection Adding a SINAUT connection The SDBs or DBs of all subscribers over which this connection
runs must be regenerated in the subscriber administration.
SINAUT connection Deleting a SINAUT connection The SDBs or DBs of all subscribers over which the deleted
connection runs must be regenerated in the subscriber
administration.
SINAUT subscriber Changing the parameter
assignment of a SINAUT
subscriber
The SDBs or DBs of all connections that run over this
subscriber must be regenerated in the subscriber
administration.
Destination subscriber
properties of TD7onTIM
Changing the parameter
assignment of a destination
subscriber of TD7onTIM
The SDBs of all TIMs with TD7onTIM that communicate with
this destination subscriber must be regenerated in subscriber
administration.