Technical data

Configuration software for SINAUT ST7
1.12 Change matrix
Software
System Manual, 07/2009, C79000-G8976-C222-07
169
1.12 Change matrix
The change matrix describes the necessary follow-up activities of the user following typical
actions in the SINAUT configuration tool.
Table 1- 9 Change matrix
Object affected Operator activity in the
SINAUT configuration tool
Necessary follow-up action
Station Adding a station -
Station Renaming a station -
Station Changing the parameter
assignment of a station
-
Station Deleting a station All SINAUT connections running over a module in this station
are then invalid and are removed the next time you open the
SINAUT connection configuration. When necessary, these must
be replaced by alternative connections. The SDBs or DBs of all
modules that were involved in these deleted connections must
be regenerated in the subscriber administration.
TIM module Adding a TIM module -
TIM module Renaming a TIM module -
TIM module Changing the parameter
assignment of a TIM module
If the parameters of a TIM module are changed, the SDBs must
be regenerated in subscriber administration only for this TIM.
Exception:
If parameters are changed in the "WAN access" tab, this affects
all SINAUT connections running over the modified WAN driver.
TIM module Deleting a TIM module All SINAUT connections running over this module are then
invalid and are removed the next time you open the SINAUT
connection configuration. When necessary, these must be
replaced by alternative connections. The SDBs or DBs of all
modules that were involved in these deleted connections must
be regenerated in the subscriber administration.
Network Adding a network -
Network Renaming a network -
Network Changing the parameter
assignment of a network
The SDBs of all the modules connected to this network must be
regenerated in the subscriber administration. In WAN networks,
these are only TIM modules, in LANs all connected modules.
Network Deleting a network All SINAUT connections running over this network are then
invalid and are removed the next time you open the SINAUT
connection configuration. When necessary, these must be
replaced by alternative connections. The SDBs or DBs of all
modules that were involved in these deleted connections must
be regenerated in the subscriber administration.
Network nodes Adding a network node -
Network nodes Renaming a network node -
Network nodes Changing the parameter
assignment of a network node
The SDBs of the module containing this network node must be
regenerated.
Exception:
When changing the telephone number, the SDBs of all TIMs in
the dial-up network must be regenerated.
Network nodes Networking a network node -