Technical data

Configuration software for SINAUT ST7
1.10 TD7onTIM software package
Software
154 System Manual, 07/2009, C79000-G8976-C222-07
Object type
Mean04W_R
Channel type:
Mean value receive
:
This channel type has no specific parameters.
Object types
Cnt01D_S
and
Cnt04D_S
The object type
Cnt01D_S
sends a counted value,
Cnt04D_S
sends four counted values.
Channel type:
Counted value send
:
This channel type has no specific parameters.
The counted value read in from the CPU must be made available by a software counter
of the CPU in the WORD format.
In TD7onTIM, the value originating from the CPU counter is compared with the value last
read from the object and the difference is added to the SINAUT counted value maintained
internally in the
Cnt01D_S
or
Cnt04D_S
object. An overflow of the CPU counter at 65535
is detected by the counted value object and taken into account.
The internally formed SINAUT counted value is stored by TD7onTIM in DWORD format
and transmitted.
Object types
Cnt01D_R
and
Cnt04D_R
The object type
Cnt01D_R
receives a counted value,
Cnt04D_R
receives four counted
values.
Channel type:
Counted value receive
:
The SINAUT counted value received from the partner object is compared with the last
received counted value and the difference is added to the value at
CountedValueOutput
.
The value is output in DWORD format so that the maximum displayable counted value is
2,147,483,647. If the maximum value that can be represented is exceeded, the counted
value starts again at 0 and counting continues in the positive numeric range.
Reset
:
If the counted value at
CountedValueOutput
is reset to zero, when the next counted value
is received, the difference is added to zero. To reset, a bit in a memory area of the CPU
is defined in the
Reset
field. The reset takes place on a signal edge change from 0 to 1.
Name: Reset
Memory area: The following options are available for the address:
- DB: Data block
- Memory bit: Memory area
- Input: Process input image (PII)
Default: Function inactive
DB No.: Specifies the DB number in the CPU if the data block memory area (
DB
)
was selected
Address
[Byte.Bit]:
Input fields for the byte and bit number in the selected memory area
Object type
Cmd01B_S
If increased reliability is required for the input of commands, setpoints and parameters, all
objects with which this data is sent should be assigned to the fast cycle. All command,
setpoint and parameter objects in the fast cycle are subjected to a 1-out-of-n check; in other