Technical data
Configuration software for SINAUT ST7
1.10 TD7onTIM software package
Software
150 System Manual, 07/2009, C79000-G8976-C222-07
trigger a different type of transmission than was specified in the basic parameters of the
object. This setting is made in the
Masks
area.
Figure 1-76 The
Masks
area in the parameter assignment dialog of the
Binary send
channel type
Name: Alarm mask
Range of
values:
Mask in hexadecimal format
Default: 00 (hex)
Explanation: Changes in masked bits in the byte of the
Binary send
channel cause an
unconditional spontaneous message transmission. Changes from 0 to 1
and from 1 to 0 are evaluated.
The corresponding bits are masked in hexadecimal format.
The
alarm mask
is only practical when the object is transmitted over a dial-
up network and the option
Conditional spontaneous
was activated in the
basic parameters of the object.
Name: Send buffer principle mask
Range of
values:
Mask in hexadecimal format
Default: 00 (hex)
Explanation: Changes in masked bits in the byte of the
Binary send
channel cause a
message transmission according to the send buffer principle. Changes
from 0 to 1 and from 1 to 0 are evaluated.
The corresponding bits are masked in hexadecimal format.
The
Send buffer principle mask
is only practical when the option
Image
memory
was activated in the basic parameters of the object.
Name: Disable mask
Range of
values:
Mask in hexadecimal format