Technical data
Configuration software for SINAUT ST7
1.10 TD7onTIM software package
Software
148 System Manual, 07/2009, C79000-G8976-C222-07
The
Trigger signal
area includes the option of an external send trigger that can be activated
with the
Active
option.
Name: Trigger signal
Memory area: The following options are available for the source address:
- DB: Data block
- Memory bit: Memory area
- Input: Process input image (PII)
Default: Function deactivated
DB No.: Specifies the DB number in the CPU if the data block memory area (
DB
)
was selected
Address
[Byte]:
Input field for the byte number in the selected memory area
Explanation: If a
trigger signal
is specified, the data of the object is transferred when the
trigger signal changes from 0 to 1.
If the trigger signal is a memory or data bit, it is automatically reset after it
has been read. The reset can, if necessary, be evaluated by the user
program, for example to display that the message was triggered.
1.10.11 Mandatory parameters of the receive channels
When you set parameters for each receive channel, the
Output address
parameter must be
set as a mandatory parameter. This is the address in the memory area of the local CPU to
which the received data will be written by TD7onTIM.
As an example of the
Output address
area, we have taken the parameter assignment dialog
of the
Binary receive
channel type.
Figure 1-75 Parameter assignment dialog of the
Binary receive
receive channel