Technical data
Configuration software for SINAUT ST7
1.10 TD7onTIM software package
Software
140 System Manual, 07/2009, C79000-G8976-C222-07
Default: 0
Explanation: In this input box, you assign the data object to the corresponding partner
object of
all
selected communication partners when the partner object
number is identical for all partners. Otherwise set 0 (zero).
Note: There is no object no. for objects of an ST7cc/sc control center!
For a send object of TD7onTIM that transfers data to ST7cc/sc, a partner
object no. = 0 can be set since the specified partner object no. is not
evaluated by ST7cc/sc.
For a receive object of TD7onTIM that receives data from ST7cc/sc, the
partner object no. = 0 must be set.
After object no. = 0 for
send objects
:
The partner object no. = 0 must be set if the object data will be sent to
several partners and the receiving objects on these partners have different
object numbers.
If partner object no. = 0 is specified and if
TD7onCPU
is used on the
partner, the ListGenerator must be installed on the partner. Only then can
the corresponding receive object to be recognized on this partner.
Partner object no. = 0 for
receive objects
:
The partner object no. = 0 must be set in the object receives data from
several partners and the sending objects on these partners have different
object numbers.
Note: If partner object no. is specified for at least one received object, the
option
Check of source address
must be deactivated in the basic settings
of this TD7onTIM. Otherwise, messages intended for these receive objects
will be rejected.
Note
With data objects of the type
Command snd
,
Setpoint send
and
Parameter send
, partner
object no. 0 (zero) is not permitted.
The
Send parameters
area:
Name: Image memory
Range of
values:
Function active: Send using the image memory principle
Function deactivated: Send using the send buffer principle