Technical data

Configuration software for SINAUT ST7
1.10 TD7onTIM software package
Software
134 System Manual, 07/2009, C79000-G8976-C222-07
DB No.: Specifies the DB number in the CPU if the data block memory area (
DB
)
was selected
Address
[Byte.Bit]:
Input fields for the byte and bit number in the selected memory area
The
PartnerStatus
system object
The optional
PartnerStatus
object can be used to monitor the availability of up to 8
communication partners. A partner can be an ST7 CPU or an ST7cc/sc control center to
which a connection was configured. TIM modules cannot be monitored with the
PartnerStatus object. The status is made available to the CPU user program in an output
byte. One bit per communication partner is reserved in the output byte to indicate the status
of the respective partner:
Status 0: Problem on partner or corresponding bit not assigned to any partner
Status 1: Partner OK
If TD7onTIM has a connection to more than 8 partners whose status needs to be monitored,
the
PartnerStatus
system object is configured more than once.
Figure 1-70 Parameter assignment dialog of the
PartnerStatus
system object
Name: Status output byte
Memory area: The following options are available:
- DB: Data block
- Memory bit: Memory area
- Output: Process output image (PIQ)
DB No.: Specifies the DB number in the CPU if the data block memory area (
DB
)
was selected
Address
[Byte]:
Input field for the byte number in the selected memory area