Technical data
Configuration software for SINAUT ST7
1.10 TD7onTIM software package
Software
System Manual, 07/2009, C79000-G8976-C222-07
133
1.10.7 Setting parameters for system objects
After the SINAUT objects for the individual subscribers have been configured, you set the
parameters for the system objects. Follow the steps outlined below:
1. Select a subscriber in the tree directory.
2. Select the required system object in the list.
The corresponding parameter assignment dialog is opened below the object list.
3. You set the parameters in this dialog.
Figure 1-69 TIM with selected system object
WatchDog
and the corresponding parameter
assignment dialog
The
WatchDog
system object
The
WatchDog
system object can be included as an option. The WatchDog indicates to the
CPU program whether the communication between CPU and local TIM is still working; in
other words, whether TD7onTIM is still reading from and writing to the memory areas of the
CPU. As long as communication is functioning correctly, a selectable output bit changes
state at five second intervals. The constant status change can be evaluated by the CPU user
program.
Parameters in the
Output Bit
area
Name: Output bit
Memory area: The following options are available:
- DB: Data block
- Memory bit: Memory area
- Output: Process output image (PIQ)