Technical data
Configuration software for SINAUT ST7   
1.10 TD7onTIM software package 
  Software 
118  System Manual, 07/2009, C79000-G8976-C222-07 
Note 
TD7onTIM cannot be used if the TIM sends or receives ST1 messages. In this case, you 
must use TD7onCPU 
This section deals only with configuration of 
TD7onTIM
. 
If the SINAUT project you are editing does not contain TD7onTIM-compliant TIM modules, 
you can skip this section and continue configuration with saving and generating system data. 
If the project you are editing contains TD7onTIM-compliant TIM modules, on which you want 
to configure the TD7onTIM software, you do this in the subscriber administration of the 
SINAUT ST7 configuration tool. 
1.10.2  Basic functions and components of TD7onTIM 
Basic functions and components of TD7onTIM 
TD7onTIM handles the sending and receiving of process data for the local CPU. Data to be 
sent by TD7onTIM, is read by the TIM over the backplane bus of the CPU, received data is 
written to the CPU. 
SINAUT communication makes use of SINAUT objects: Which data is to be sent or received 
can be configured over standardized data objects. These are collected in the TD7onTIM 
standard library. This library also contains the system objects with which system information 
is displayed and with which system functions are activated and set. 
The parameter assignment for TD7onTIM is made in the subscriber administration of the 
SINAUT ST7 configuration tool in the following steps: 
●  Setting basic parameters for TD7onTIM 
●  Specifying the parameters specific to the destination subscribers 
●  Inserting system objects and assigning parameters to them 
●  Inserting data objects including their send and receive channels and assigning 
parameters to them 
The basic settings for TIM subscribers with TD7onTIM 
For each TIM with TD7onTIM, several settings must be made that are always required when 
working with TD7onTIM, for example specifying the read/write cycle. The settings are made 
in the basic settings for TIM subscribers with TD7onTIM. 
The parameters specific to the destination subscribers 
Each TIM with TD7onTIM can exchange data with one or more partners, known as 
destination subscribers. Which subscribers in the project are suitable as destination 
subscribers depends on the connection configuration. Here, you specify which TIM with 
TD7onTIM will have a connection with which SINAUT subscriber in the network. 
Several settings are required for each of the possible destination subscribers that apply to 
data traffic between the TD7onTIM of a project and this subscriber, for example whether the 