Technical data
Configuration software for SINAUT ST7
1.9 Subscriber administration in the SINAUT configuration tool
Software
System Manual, 07/2009, C79000-G8976-C222-07
115
● Max. allowed disruption time [s]
Here, you can enter the tolerance time for connection disruption detected by the TIM. If
there is still a disruption on the connection when the set time has elapsed, the disruption
is signaled to all connection partners of the disrupted station.
If networks are regularly disrupted, it may be useful to increase the default value of
10 seconds. Increasing the allowed disruption time delays signaling of station failures and
so reduces the number of organizational messages when stations return.
● Baud rate (TIM - modem) [bps]
This is the speed at which the TIM and modem communicate. The default baud rate is
9 600 bps and cannot be changed.
"MSC Login" box
Here, you configure the two mandatory boxes "User name" and "Password" for all MSC
stations/node stations with GPRS or DSL connection. The data is required for establishing
the connection and logging on with the MSC master.
● User name
Enter the user name here with a maximum of 64 characters.
The following characters are permitted: a...z, A...Z, 0...9, comma (,), period (.), hyphen (-)
and underscore (_)
● Password
Enter the password here with a maximum of 30 characters.
The following characters are permitted: a...z, A...Z, 0...9, comma (,), period (.), hyphen (-)
and underscore (_)