Technical data
Configuration software for SINAUT ST7
1.9 Subscriber administration in the SINAUT configuration tool
Software
114 System Manual, 07/2009, C79000-G8976-C222-07
Configuring an MSC station/node station
Figure 1-62 "MSC Station Properties" dialog
In this dialog, you configure the access data for the connected network.
"GPRS Network Access" box
In this box, you configure the Internet access data for GPRS stations (with MD720-3). For
stations with a DSL connection, you configure the relevant data on the DSL router.
● Provider name
If you have not yet assigned a GPRS provider,the first provider from the list of GPRS
providers is entered as default. You can assign the provider in the MSC station list, see
section
"MSC Station List" (Page 110).
● PIN of the SIM card
Here, you enter the PIN of the SIM card for the MD720-3.
● Additional transmission time [s]
This is an offset added to the transmit retry time. The transmit retry time is calculated
automatically on the TIM. The character delay time is also calculated from the "additional
transmission time" parameter (character delay time = additional transmission time divided
by 5).
For GPRS networks, a value of 10 seconds as in the default setting is normally adequate.