Technical data

Configuration software for SINAUT ST7
1.9 Subscriber administration in the SINAUT configuration tool
Software
System Manual, 07/2009, C79000-G8976-C222-07
107
For the CPU, you can specify a name with up to eight characters (
CPU short name
). This
short name can be inserted with a placeholder string in SMS messages later during
SMS
message configuration
. As default, the short name has the first eight characters of the CPU
name.
SMS DB data
dialog
If you select an SMS DB in the
SMS Configuration
tab and click on the Edit button, the
SMS
DB data
dialog opens. This dialog displays and allows you to configure the data of the
selected SMS DB.
Figure 1-58
SMS DB data
dialog
The following parameters are available:
DB No.
:
The number used for the SMS DB. The number can be modified, the availability of the
specified number on the current CPU is checked. If the number is already assigned by a
DB of the CPU user program, an error message is displayed. SMS DBs on the other
hand can be overwritten.
DB short name
:
As default, the SMS DB short name has the first eight characters of the CPU name. For
the SMS DB, you can specify a DB Short name with up to eight characters. This DB short
name can be inserted with a placeholder string in the message text of SMS messages
later during
SMS message configuration
.