Symptom Detected Problem Solution
AL1
Communication Error with HRV
1. Check wiring connections between HRV and Fan Controller.
2. Check door switch on HRV.
3. Cycle power to appliance; contact NTI.
AL2
Plenum Temperature Limit of
160ºF Exceeded
1. If plenum is hot, check operation of blower fan; contact NTI.
2. If plenum is not hot, check plenum sensor and wiring for shorts or damage.
3. Remove plenum sensor, PSO should be displayed, if so replace plenum
sensor, if not inspect wiring from Terminal Strip to Fan Control. Replace Fan
Control if necessary.
AL7
‘Boiler Control Error’
Fan controller has failed to receive
run status from Boiler Control.
1. Check for error code on Boiler Control.
2. Check control wiring from Boiler Control to Fan Control (Pins 17 and 18 on
Fan Control – See wiring schematic in Section 8.2).
AL8
(& Blower Off)
‘Furnace Blower Error’
Blower has failed to meet a
minimum speed.
1. Check for 120V to blower; ensure door switches are making the circuit.
2. Check wiring from Pin 6 at Fan Control (white wire) to Pin 15 at blower
motor.
3. Check for 24VAC at blower Pin 15, if present replace blower, if not replace
Fan Control.
AL8
(& Blower On)
‘Furnace Blower Error’
Control has failed to sense that the
blower has reached a minimum
speed.
1. Check wiring from Pin 5 at Fan Control (black wire), to Pin 16 at blower
motor.
2. Check for 3-5VDC at blower Pin 16, if present replace blower, if not replace
Fan Control.
‘PSC‘
‘Plenum Sensor Circuit Closed’ 1. Check for chaffed wires on plenum sensor.
‘PSO‘
‘Plenum Sensor Circuit Open’
1. Check for proper connection of plenum sensor to terminal strip.
2. Check for broken plenum sensor wire.
Fan Controller (Blue Face)
F3.2 Flashing
Lack of 24 V at fan controller
1-Check/Replace 2A fuse – blown fuse indicates 24V supply shorted to ground, or
excessive load.
Two Flashes
on Fenwal
The Fenwal controller thinks that
there is a flame prior to ignition.
Indicates Ignition Lockout.
If the combustion sequence is normal, and there is no flame prior to ignition, the
Fenwal control is defective, and must be replaced.
If the condensate drain gets blocked, the boiler will become flooded and terminate
operation as the flame rod becomes immersed. This will damage the flame probe.
To correct, free the drain blockage, and permanently prevent it from reoccurring.
Remove and dry off the probe. Reinstall the probe and try for ignition, if it fails to
stay lit, leave the fan run for up to three hours to dry out the insulation and probe.
Fenwal
Three
Flashes on
Fenwal
“Ignition Lockout”
1. Reset Boiler so it will attempt to ignite.
2. Check for proper operation of ignition components. Make sure igniter glows
and gas valve opens.
3. Check for proper line pressure at gas valve when it opens.
4. If boiler lights check for flame signal between FC1 And FC2 on Fenwal
control (If lower then 1.2 DC µAmps see “Boiler will not stay lit”).
5. Check combustion properties.
Reset calculation being used to
lower HI setting.
If OD probe is being used, the HI setting will be calculated using formula in
Section 8, adjust RES setting as necessary.
General
Burner shuts
off before
set-point
temperature
is reached
(and burner
light goes out)
Thermostat is satisfied
1. If the thermostat demand light is turning off, the thermostat has satisfied.
2. 2-If DHW temp light is turning off; the aquastat or call for domestic has been
satisfied.