User manual
WIRING AND INSTALLATION HARDWARE LAYOUT
MATRIX BACnet Router User Manual (6/6/2007) 2-3
2.1 HARDWARE LAYOUT
Connections to the MATRIX BACnet Router are made via ports located on the left side of the controller
board. As illustrated below, the device has ports for Main Power, EIA-485 network connectivity and
Ethernet connectivity. Depending on the variant of MATRIX BACnet Router purchased, your application
may involve using only one of the two available EIA-485 network ports. Other unused ports such as RS-
232 and USB are reserved for future use.
Figure 2-1 MATRIX BACnet Router Network Controller Board Layout
PWR PWR
12-29 VDC / VAC
2.7A (MAX)
J1
LINE
J3
RS-485
TXD
RXD
PERR
BERR
N+
N-
SH
J2
SW3
TERM
BIAS
J5TELCO
N+
N-
SH
61
SW2
TERM
BIAS
RS-485
TXD
RXD
PERR
BERR
3.3V
5V
24V
A
U1
S2 S1
SW1
ATTN
U2
RS-232
Power Input
PWR
PWR
RS-485
NET
NET
SH
+
-
RS-485
NET
NET
SH
+
-
USB
10 / 100
Ethernet
Termination Off
(Factory Setting)
Biased
(Factory Setting)
RS-485 Biasing -
SW2.2 and SW3.2
RS-485 Termination -
SW2.1 and SW3.1