User guide
Temperature Controller iB6 / iB12
© Copyright Mastip Technology Limited. Information subject to alteration. V1.02 www.mastip.com
29
6.0 PID Controller Tuning
6.1 Introduction
iB6 and iB12 Temperature Controllers support automatic tuning for control of zones running in 
CompuCycle Normal (closed loop) mode. 
By default, every iB6 and iB12 controller is configured to execute the Autotune operation the first 
time it is powered up, then to disable the Autotune feature, even if Autotune was not successful. 
The Autotune operation overwrites any existing proportional band and derivative (rate) parameter 
values that were previously configured.
All iB6 and iB12 controllers in a single process should be Autotuned simultaneously, so that 
interactions between zones during tuning parallel the interactions expected while the controllers 
are in use. 
6.2 Procedure for Autotuning
To Autotune:
1)  Make sure the controller is in Idle state (only the green C or F LED lit).
2)  After configuring any parameters that you want to change from the defaults, enter a setpoint that 
is representative of the setpoint you expect to use when the selected zones are in Normal mode 
operation.
3)  If Autotuning has been attempted in the past, the Autotune feature may be disabled. To force an 
Autotune operation, use the Control Config menu to set the PID Autotune parameter to Enable. 
4)  Cycle the power to the controller.
5)  At this point the controller may execute a CompuStep
®
 soft start.
 • Ifyouwantthesoftstarttocontinuetoitsnormalconclusion(recommended),
do not press any buttons. 
 • Ifyouwanttoterminatethesoftstart(notrecommended),usethemode 
button
to set the selected zones mode to Normal. 
Typical Autotune PV Profile
SV
Heat Storage Test
Heat On
Heat On
Heat Off
Response Test
Starting Conditions Test