User guide

Temperature Controller iB6 / iB12
© Copyright Mastip Technology Limited. Information subject to alteration. V1.02 www.mastip.com
27
Name Applies to Range/
Choices
Default Description & Interactions
Selected Zones
All Zones
Closed Loop Control
Open Loop Control
Set Superv.
Password
  
100 to 999 100 = Off Password needed to access
parameters in Superv
[Supervisor] Config menu
Fail Safe
Action
Off
Auto
Average
Fixed Output
Pct.
Auto Average Output action to be used
when controller detects an
open or reversed sensor: off,
automatically calculated based
on past good output values (if no
history of Normal mode output
values, then zero), or failsafe
fixed output percent
Low Reading
Lowest process value for
selected zone since the last time
the reading was reset by pressing
the up or down arrow button
High Reading
Highest process value for
selected zone since the last time
the reading was reset by pressing
the up or down arrow button
High Safety
(High
Temperature
Safety Limit)
1 to 537 °C
33 to 999 °F
OFF Output will be turned off if
process value reaches this
temperature
Fail Safe FOP
(fixed output
percentage)
0 to 100% 0% Output percent used only if open
or reversed sensor is detected
and Fail Safe Action is set to
Fixed Output Pct.
Loop Break
Time (sec.)
OFF
10 to 999
seconds
300 seconds Time period during which the
input should change 1% of
supported sensor span (5.37 °C
or 9.67 °F) in response to output
action if the sensor is working
correctly and the input wiring is
intact
5.7.2 Supervisor Parameters and Settings
5.0 Parameter Characteristics