5.6 Alarm Parameters
5.6.1 Introduction
High and low deviation alarms are supported for each zone. (Section 4 contains information
about alarm indication and effects on outputs.)
You can use the Alarm Config menu to specify for the selected zone(s):
• how many seconds after zone is taken out of Idle the controller should wait before indicating a
low alarm (Alarm Inhibit)
• number of degrees the process value must exceed the setpoint before the zone goes into
alarm (High Deviation)
• number of degrees the process value must fall short of the setpoint before the zone goes into
alarm (Low Deviation)
• the number of seconds the audible alarm on the iB6 or iB12 unit will be silenced when
(on
the front of the controller’s case) is pressed; this value applies to ALL zones in alarm.