User guide
© Copyright Mastip Technology Limited. Information subject to alteration. V1.02 www.mastip.com
16
Temperature ControlleriB6 / iB123.0 User Interface
3.7 Configuration Menus and Factory Settings
The table below shows all configuration menus, the parameters in each menu, and the factory 
settings. Information about each parameter is in Section 5.
At the factory, all zones settings are identical. 
When a parameter is accessed, the display of its name alternates with the display of its current value.
Menu Parameters Factory Setting
Input
Config
Bias 0°
Low Setpoint Limit 0 °C (32 °F)
High Setpoint Limit 537 °C (999 °F)
Input Type Depends on input type specified 
when the unit was ordered
Boost
Config
Boost Type (applies only to zones 
running in Normal mode; zones 
running in Manual mode always use 
Boost Percentage; see below)
Closed loop
Boost Duration Boost Off
Boost Setpoint 25 °C (77 °F)
Boost Percentage 0
Control
Config
Standby Type Open Loop
Standby Setpoint 25 °C (77 °F)
Standby Percentage 0
Proportional Band 24
Derivative [PID rate] 7 seconds
PID Autotune (when it will be 
performed)
Once at next power-up, and then 
disabled, even if tuning was not 
successful
Startup Mode (when zone is taken 
out of Idle with run/idle button  )
Last Active Mode (most recent 
operating mode)










