Product Specifications
Specifications
General specifications
Output voltage 230/240 V - 50/60 Hz (selectable)
Output waveform true sine
Nominal battery voltage 12 V
Recommended battery capacity >= 360 Ah
Continuous power at 25 °C / 77 °F, cos phi 1 3500 W
Continuous power at 40 °C / 104 °F, cos phi 1 3500 W
Peak load (3 s) < 4500 W
Peak load (< 0.2 s) < 6000 W
AC connection hardwired + plug connection EU (Schuko), UK plug (code 28213500), or
NZ/AU plug(code 28413500)
Galvanic isolation yes
Efficiency 90 %
Parallel configuration yes, up to 15 units
3-Phase configuration yes, 3 units
Display/read-out LED indication: battery voltage, load level, status
Alarms potential free alarm contact
Dimensions, hxwxd 283 x 496 x 128 mm
11.1 x 19.5 x 5.0 inch
Weight 10 kg
22.0 lb
Compliance CE, E-mark, RCM
Technical specifications
Technology high frequency, input & output fully isolated
Low battery voltage, switches off at 10.5 V
Low battery voltage, switches on at 12.5 V
High battery voltage, switches off at 16.5 V
High battery voltage, switches on at 14.5 V
Input current (nominal load) 350 A
No-load power consumption (ON mode) < 3.6 A
No-load power consumption (energy saving mode) < 1.4 A
Minimal DC fuse (slow blow) 400 A
Minimal cable size 120 mm²
Harmonic distortion typical < 3 %
Cos phi all power factors allowed
Transfer system integrated, automatic (inverter to grid: 8~10 ms, grid to inverter: 16~50
ms). Not for parallel & 3-phase operation (external transfer system
possible)
Temperature range (ambient temp.) -20 °C to 60 °C, derating power > 35 °C
-4 to 140 °F
Cooling temperature and load controlled fan
Protection degree IP21, horizontal wall mounting
Protections over-temperature, overload, short circuit, high/low voltage, reverse
polarity (fuse)
MasterBus compatible yes, using a MasterBus AC Master Interface