Output frequency selection
Frequency DIP switch 3
50 Hz OFF
60 Hz ON
To save energy from the battery in no load operation, DIP switch 4 can be used to enable the Power
Saving Mode.
Power Saving Mode
Mode DIP switch 4
Power Saving OFF OFF
Power Saving ON ON
The Power Saving Mode scans the output and compares the detected load to the set threshold
values. When a load is detected which is lower than the Power Save threshold value, the inverter
switches into Power Saving Mode. When a load is detected which is higher than the Wake Up
threshold value, the inverter is switched on.
The threshold values for Power Save and Wake Up are both set with the variable resistor. The
variable resistor is located on the right of the DIP switches. The minimum and maximum threshold
values are described in the following table.
Power saving load adjustment
Threshold type Min Max
Power save threshold 20 VA 110 VA
Wake up threshold 40 VA 160 VA