Technical data

4. GENERAL REQUIREMENTS
MKA4CAT0UKAG4MG/Rev. 1-01/2009
04
4.1 Standards and certifications accordance with the following Electrical and Electronic Equipment.
international standards:
MASTERGUARD GmbH is certified by the 4.3 Neutral/earth
German TÜV as a company with a quality EN62040-1-1, EN 60950 (RD); general
Series A neutral output is not connected
and environmental management system and safety requirements
to the
earth and battery negative voltage
EN62040-2 Class C2, EMC requirements
in accordance with standards ISO 9001
is referenced to neutral output.
and ISO 14001.
Series A shall also bear the TÜV and
Series A shall not modify the neutral
UL/cUL certifications for safety.
Series A shall carry the CE mark in
state, with the exception in battery mode
accordance with the Safety Directive
4.2 RoHS
due to the backfeed protection.
2006/95/EC and the EMC Directive
2004/108/EC (superseding the
Series A voluntarily complies with the
89/336/EEC, 92/31/EC and 93/68/EEC
requirements of the Directive 2002/95/EC
Directives).
regarding Restriction of the Use of Certain
Hazardous
Substances (RoHS) in
Series A is designed and manufactured in
5. BATTERY MANAGEMENT
5.1 Battery configurations
The UPS shall automatically detect the
display.
number of external battery packs
A pre-alarm signal shall be activated
Series A shall include the configurations
before the end of battery back-up to alert
connected via communication cables
shown in the tables below:
(bundled with the batter y packs)
the operator
(BATTERY LOW signal). By
Batteries shall be sealed, lead-acid and
default, this signal shall be activated when
interconnected between the UPS and the
maintenance-free. Internal batteries in the
the remaining battery capacity goes
battery packs. Internal calculations about
UPS are easy-swappable. UPS includes
below 25% of the total capacity. This value
back-up time are done according to the
quantity of battery packs connected. It is
recommended a maximum of 4 external
battery packs to each UPS.
Additional battery arrangements may be
configured, as well as external battery
chargers. Please check the details with
the local Chloride office for these
customized configurations.
5.2
Back-up times
The above battery configurations shall
provide the following back-up times.
internal protection against overvoltages
can be configured by the user (via LCD
They are typical back-up times assuming
and deep discharge protection to
display) to 25%, 50% or 75%.
resistive load, batteries fully charged and
maximize reliable battery life.
ambient
temperature of 25ºC. These
An end-of-battery-life alarm shal l be
values may vary depending on these
Test of battery system shall be run upon
activated 4 years after commissioning to
conditions. 700 VA model does not allow
user request (via front panel) or at regular
alert the operator that batteries should
be
connection of external battery packs.
intervals (daily, weekly or monthly). These
replaced. This alarm can be deactivated by
intervals can be configured via LCD
the operator via front panel.
Battery Pack
BP-A1000/1500-T
BP-A1000/1500-RT
BP-A2000/3000-RT
Configuration
2x3x7.2Ah (36Vdc 14.4Ah)
2x3x7Ah (36Vdc 14Ah)
2x6x45W (72Vdc 90W)
UPS Model
A700-T
A1000-T/A1000-RT
A1500-T/A1500-RT
A2000-RT
A3000-RT
Configuration
1x2x7.2Ah (24Vdc 7.2Ah)
1x3x7.2Ah (36Vdc 7.2Ah)
1x3x45W (36Vdc 45W)
1x6x7.2Ah (72Vdc 7.2Ah)
1x6x45W (72Vdc 45W)
1000 VA
models
UPS
UPS + 1BP
UPS + 2BP
UPS + 3BP
UPS + 4BP
160 W
37 min
158 min
254 min
397 min
476 min
400 W
15 min
55 min
97 min
174 min
220 min
560 W
11 min
38 min
69 min
99 min
161 min
800 W
6 min
25 min
46 min
67 min
89 min
700 VA
model
UPS
110 W
35 min
280 W
15 min
390 W
10 min
560 W
5 min
1500 VA
models
UPS
UPS + 1BP
UPS + 2BP
UPS + 3BP
UPS + 4BP
240 W
25 min
84 min
180 min
234 min
331 min
600 W
10 min
34 min
62 min
90 min
140 min
840 W
7 min
24 min
43 min
63 min
83 min
1200 W
3 min
16 min
28 min
42 min
56 min
MASTERGUARD Series A
UPS from 700 VA to 3000 VA