Technical data
MKA4CAT0UKAG4MG/Rev. 1-01/2009
09
9. MECHANICAL DATA
9.1 Enclosure 9.2 Ventilation 9.3 Installation of rack/tower units
The UPS shall be housed in an Forced air cooling shall ensure that all The rack/tower units can be rack-
enclosure with removable front panels the components are operated within mounted into 19” cabinets or installed
(UPS internal batteries shall be their specification. Airflow shall
be as tower (floorstanding). The required
accessible from the front panel) and controlled according to load demand. mounting elements for both situations
IP20 protection. Standard colour of the The cooling air entry shall be on the are either bundled with the units or
enclosure shall be RAL7016 (grey front panel
and the air exit on the rear available as options.
anthracite), thus providing an optimum side.
alternative for most environments.
10. TECHNICAL DATA
MASTERGUARD Series A
UPS from 700 VA to 3000 VA
A 700-T
700 VA 1000 VA 1500 VA 2000 VA 3000 VA
Tower
157x245x438 157x245x438
438x86.5(2U)x482
157x245x488
438x86.5(2U)x482
438x86.5(2U)x657
438x86.5(2U)x657
12.3
Tower
15
Rack/Tower
17.9
Rack/Tower
20
Rack/Tower
26
Rack/Tower
31
Tower
17.6
Advanced on-line double conversion
200 - 240 V
191 - 264 V
50/60Hz auto-selection
50/60Hz +/-5% (40-70Hz in Frequency Converter Mode)
3%
50/60Hz ±0,5% (same as input or selectable in Frequency Converter Mode)
Sealed maintenance-free lead acid (VRLA)
Advanced battery care and external battery pack autodetection
Yes
Yes
0 -
40 ºC
-15ºC / +40ºC
0-3000m / 20% to 90% (non condensation)
RS232/USB / status signals
6*Imaxpk<1 ms
1 slot for SNMP or volt-free contacts card
200 / 208 / 220 / 230(default) / 240 V
From nominal voltage -10% to 284 V
120 - 284 V
140 - 284 V
700/630
86%
39
1000/900
86%
39 40
1500/1350
86%
39 40
2000/1 800
88%
46
3000/2 700
90%
46
A1000- T
A 1000 -RT
A 1500 -T
A1500- RT
A2000- RT
A3000 -RT
UPS Rating
Technology
Nominal input voltage (VAC)
Nominal input frequency (Hz)
Operative input frequency range (Hz)
OUTPUT
(2)
Nominal output voltage (VAC)
Voltage regulation (%)
Output frequency (Hz)
BATTERIES
Type
Battery management
(3)
Typical autonomy
GENERAL
(4)
Efficiency in line mode (%)
Typical acoustic noise in on-line mode (dBA)
Inrush current
CONNECTIVITY
(5)
Communication Ports
Communication Slot
Remote Power Off (RPO)
Remote On/Off (ROO)
ENVIRONMENTAL
Operating temperature
Storage temperature
Altitude & Relative humidity
MECHANICAL
Size (WxHxD, mm)
Weight (kg)
Housing
(1)
Output Power (VA/W)
INPUT
Operative input voltage range @ nominal power(VAC)
Maximum operative input voltage range
Operative input voltage range in ECO/bypass mode (VAC)
8 min 9 min 6 min
9 min
6 min
(1) Output power with external battery packs is: 1000 VA models: 1000 VA/800 W, 1500 VA models: 1500 VA/1200 W, 2000 VA
models: 2000 VA/1600 W, 3000 VA models: 3000 VA/2400 W. For 200, 208 and 220 Volts the output power factor is 0.8.
(2) For output nominal voltages 200 V
and 208 V, there is a power de-rating of 20% and 10% (the unit's nominal power is reduced
by 20% and 10%) respectively.
(3) Considering an output resistive load of 75%, 0.8 output power factor and batteries fully charged
(4) These values have been rounded.
(5) Both ports cannot be used simultaneously.
Note: The information shown in the table above corresponds to a nominal voltage of 230 V. For other conditions, please check
specification.