Technical data

13 Options
MASTERGUARD Series SIII
UPS Systems from 60 to 800 kVA
26
MKA4CAT0UKSIII/Rev. 11-11/2004/UK
13.17 Customer interface board
It shall be possible to increase the
number of input/outputs described in
section 8.8 by the adding of an
additional board. These input/outputs
can be used to monitor smoke, fire
and water detectors, as specified by
the user. Each board shall comprise:
•Four digital inputs (from voltage
free contacts)
•Two outputs - voltage free contacts
(1A 30V AC/DC)
13.18 Telephone switch for LIFE.net
The installation of the telephone
switch for LIFE.net shall allow the user
to use a telephone line normally
reserved for other purposes (e.g. fax
or telephone).
13.19 MopUPS Shutdown and
monitoring software
The main function of MopUPS
software shall be the safe shutdown of
the operating system in the event of a
power failure. Other functions include:
1. Automatic communications for events;
e-mail, SMS, etc.
2.Saving to file of event log and status
information
3.Viewing and monitoring of UPS in
realtime
4.Programmed system shutdown
5.Remote monitoring of UPS
connected to network server using
Named Pipes or TCP/IP
13.20 ManageUPS adapter
This option shall include a complete
package (including slot card adapter) to
ensure monitoring and control of the
networked UPS through TCP/IP
protocol. The adapter permits:
UPS monitoring from NMS via
SNMP
UPS monitoring from PC via a Web
browser.
Dispatch of e-mail messages on
occurrence of events
ManageUPS, in conjunction with
MopUPS, shall also permit safe
shutdown of the operating systems.
13.21 PPVIS surveys Monitoring
Software
In addition to full monitoring capability,
this powerful software connectivity
tool allows complete access to the
UPS configuration parameters.
Therefore the user must attend a
specialist training session with
MASTERGUARD Service Engineers
before being granted access to PPVis.
The survey images as displayed below
supply the user with essential
information on the connected UPS:
State indication - power flux survey
Current state of components (UPS)
Display of output voltage, UPS
performance and load currents
Number of power failures
•Battery cell voltage
•Available backup time
The oscilloscope - measuring of
network or load conditions
Dual-carrier measurement of the
curves of input, output voltages or
currents.
•Flexible definable trigger conditions
capable of being coupled with the
most varied events, such as when
a mains failure occurs
13.14 Empty battery cubicle
Matching empty battery cubicles shall
be available including:
Cubicle
Disconnecting means
•Fuses
Safety screen
Connection terminals
UPS/battery connection cables (for
adjacent installations)
Three cubicle sizes shall be available:
Width Depth Height Weight
(mm) (mm) (mm) (kg)
Type A 820 858* 1780 220
Type B 1020 858* 1780 250
Type C 1020 1058* 1980 350
* including front handle; without
handle 830/1030 mm
13.15 Empty options cubicle
A matching cubicle shall be available
for customised applications such as:
Input/Output voltage matching
transformers
Customised distribution boards
Customised applications.
The options cubicle shall be available
in four sizes:
Width Depth Height Weight
(mm) (mm) (mm) (kg)
Type A 820 858* 1780 180
Type B 1020 858* 1780 200
Type C 1420 858* 1780 250
Type D 1020 1058* 1980 300
* including front handle; without
handle 830/1030 mm
13.16 Use as Frequency Converter
Series S
III may be programmed for use
as a frequency converter (50Hz in –
60Hz out or 60Hz in – 50Hz out) for
operations without a battery bank
connected. In this operational mode,
the data shown in tables 11 and 12 may
vary (e.g. output overload capability).
Please contact MASTERGUARD
Te chnical Support for details.
Tecnico-SIII-MG 10-11-2004 8:22 Pagina 26