Technical data
12 Technical data (250 to 800 kVA)
MASTERGUARD Series SIII
UPS Systems from 60 to 800 kVA
24
MKA4CAT0UKSIII/Rev. 11-11/2004/UK
UPS Unit Rating 250 300 400 500 600 800
12.7 Environmental
Temperature: Operating (°C) 0-40
Max average daily (24hrs) (°C) 35
Maximum (8hrs) (°C) 40
Maximum relative humidity @ 20°C (non condensing) (%) up to 90
Elevation without derating (m) (-1.2% Pn every 100 m above 1000 m)
1000
12.8 Battery
Optimum battery temperature (°C) 15-25
DC power (kW) 213 254 339 423 508 677
Recommended no. cells: VRLA
(5)
240
WET 240
NiCd 375
End of discharge voltage (V) 396
End of discharge current (A) 538 645 855 1069 1283 1710
Battery current setting range (A) 15-80 15-80 20-110 25-135 25-160 30-120
(1) @ 234 cells and nominal output power;
(2) for tolerance see IEC/EN 60146-1-1or DIN VDE 0558;
(3) valid for 60-500kVA range only in PFC Mode;
(4) including front handle; without handle 830/1030 mm
(5) permitted number of cells = 234-246
(6) only with battery connected
(7) Units rated 250, 300, 400 and 500 kVA can supply loads with PF up to 0.8, leading or lagging, at full nominal output power. For the same ratings, loads with
PF up to 0.9, leading or lagging, can be supplied at full nominal output power with limitation in the maximum value of battery recharge current. Please contact
MASTERGUARD Technical Support for further details. For 800 kVA and 600 kVA for loads with PF> 0.8 or leading please contact MASTERGUARD Technical Support.
(8) Imax input can be deduced from the maximum input power @400V, recharge mode.
Note:
The data shown are typical and not definable in other ways; furthermore the data refer to 25°C ambient temperature and PF= 1 where not specified.
Not all the data shown apply simultaneously and may be changed without prior warning.
If the options described in chapter 13 are added, the data shown in table 12 may vary.