Technical data

MASTERGUARD Series SIII
UPS Systems from 60 to 800 kVA
UPS Unit Rating 60 80 100 120 160 200
11.4 Inverter output
Nominal apparent power @ PF 0.8 lagging 40°C (kVA) 60 80 100 120 160 200
Nominal active power (kW) 48 64 80 96 128 160
Nominal output current (A) 87 116 145 174 232 290
Nominal apparent and active power @ PF >0.8,
lagging or leading, 40°C See note (7)
Overload at nominal output voltage and
0.8 PF for 10 min (%) 125
Overload at nominal output voltage and
0.8 PF for 1 min (%)
(6)
150
Short circuit current capacity for 5 seconds (10ms) (%) 150 (200)
Nominal output voltage (V) 400 (380/415 selectable) 3Ph + n
Nominal frequency (Hz) 50/60 (selectable)
Voltage stability in steady state condition
for input DC variations and 100% load variations (%) ±1
Voltage stability in dynamic condition for 100%
nominal load step variations or DC input variations (%) Complies with IEC/EN 62040-3, Class 1
Voltage stability in steady state for 100%
unbalanced loads (0, 0, 100) (%) ±3
Output frequency stability
In synchro with the mains (%) ±0.75 (1.5, 2.5, 6 selectable)
With internal quartz oscillator
(%) ±0.05
Frequency slew rate (Hz/sec) <1
Output voltage distortion with 100% linear load (%) <3
Output voltage distortion @ reference
non linear load as for IEC/EN 62040-3 (%) <5
Load crest factor without derating (Ipk/Irms) 3:1
Phase angle precision with balanced loads (degrees) 1
Phase angle precision with 100%
unbalanced loads (degrees) <±2
DC/AC efficiency
(2)
: Half load 92.0 92.5 93.0 93.0 93.5 93.5
Full load 93.0 93.0 93.5 93.5 94.0 94.0
Neutral conductor sizing see Chapter 6.5
Output power upgradability with temperature: At 25°C (%) 110
At 30°C (%) 105
At 40°C (%) 100
11 Te c hnical data (60 to 200 kVA)
18
MKA4CAT0UKSIII/Rev. 11-11/2004/UK