Technical data
8 Monitoring and control, Interfaces
MASTERGUARD Series SIII
UPS Systems from 60 to 800 kVA
10
MKA4CAT0UKSIII/Rev. 11-11/2004/UK
8.1 General
The UPS shall incorporate the necessary
controls, instruments and indicators to
allow the operator to monitor the system
status and performance, and take action
where appropriate. Furthermore,
interfaces allowing extended monitoring
and control, in addition to service
functions shall be available. UPS rated
from 60kVA up to 500kVA feature a
mimic panel with graphical LCD display
as described in the section below, while
UPS rated 600kVA and 800kVA feature a
specific LCD and LED mixed mimic panel
(for further details refer to the User
Manuals pertaining to these models).
8.2 Mimic panel (60 to 500kVA)
The control panel of Series S
III includes a
back-lit Liquid Crystal Display (LCD of
ON OFF
KEYBOARD
8.3 Start and Stop Inverter push
buttons
The Start and Stop push buttons are
integrated into the mimic panel board,
and have the following predefined
functions:
The control shall incorporate a safety
feature to prevent inadvertent
operation yet still allow for rapid
shutdown in the event of an
emergency. To stop the inverter the
user must press and hold the Stop
button for two seconds. An audio
alarm shall be activated during this
delay time.
Start inverter operation
Stop inverter operation
eight lines x 12 characters, displaying
graphic diagrams and symbols) for
complete UPS monitoring and control.
Complete access to all LCD menus is
possible through navigation push buttons
located below the screen. This navigation
group includes two buttons - “up” and
“down” - for menu scrolling and two
software-assigned push buttons: the
function linked to these two buttons is
displayed on the lower right and lower left
corners of the LCD during navigation.
A single-line diagram of the UPS is
continuously displayed on the default
page (for reference see figure 1). The
main functional blocks and power paths
of the UPS are displayed using simple
universal technical symbols, instantly
communicating the overall status of the
UPS. The same screen also permanently
displays the output load percentage
measurement, using three histograms
(one for each output phase). In the case
of the UPS not in normal functioning
mode, it is possible to access the
“Warning and Alarm” summary page
directly from the default page. Warnings
and alarms shall be identified by text
strings and codes. In battery operation,
the display shall switch between warning
code and estimated backup time in
minutes.
After 30 seconds of inactivity (i.e. without
buttons being pressed) the display
reverts to the default page.
The text displayed by the LCD shall be
available in English, Italian, French,
German, Spanish Portuguese, Turkish
and Chinese, selectable by the user.
Graphical LCD
screen
Navigation buttons:
left soft-key,
up and down button,
right soft-key
“Inverter On”
push button
“Inverter Off”
push button
“Alarm” LED
“System Normal”
LED
Commands key lock
“Warning” LED
“Reset” push button
(e.g. audible signal
silence for warning
and alarm conditions)
Tecnico-SIII-MG 10-11-2004 8:22 Pagina 10