TROUBLESHOOTING GUIDE.
Trouble, Alarm Codes Causes Corrective Actions
Pressure transducer alarm
PRSA
Bad transducer
Out of range
Loose wire
Wrong hook-up
Replace the pressure transducer
Turn off power for a few seconds, turn back on
Toghten the connections
Wire correctly
Outlet sensor TS2 fails
STSA
Mechanical damage
Connection wire loose
Overheated
Out of range
Replace the sensor
Tighten the connection wires
When brazing suction line, take out the sensor
Install the sensor after brazing
Room sensor TS3 fails
ATSA
Mechanical damage
Connection wire loose
Overheated
Out of range
Tighten the connection wires on the controller
terminal
The room sensor can be replaced by surface sensor
Coil/defrost sensor TS1 fails
CTSA
Mechanical damage
Loose connection wire
Overheated
Out of range
Tighten the connection wires on the controller
terminal
Let the sensor cool down to application temperature
range: –50
o
F to +103
o
F
Replace failed sensor
Aux sensor fails (if provided)
T4SA
Mechanical damage
Loose connection wire
Overheated
Out of range
Tighten the connection wires on the controller
terminal
Let the sensor cool down to application temperature
range: –50
o
F to +103
o
F
Replace failed sensor
Low superheat
LOSH
Superheat setting too low
Wrong locations of TS2
Sensors may be loose
Uneven feeding of coil circuits
Overcharge of refrigerant
Defective electric expansion valve (EEV)
Compressor stops
Change to correct set point
Make sure the distributor is feeding each circuit
evenly
Insulate the sensors with foam tape
Use correct refrigerant charge
Check EEV wiring
Replace defective EEV
Check compressor
High room temperature
HITA
Insufficient refrigeration
Heat load too large
Compressor fails or high pressure cuts out
Evaporator fans may not run
Door open for too long
Coil iced-up
Check system design to select a sufficient system
Replace failed compressor
Fix the evaporator fans
Keep the cold room door closed during refrigeration
Check possible air leak through the walls of cold
room
Low room temperature
LOTA
Inproper low temp setpoint
Over designed system
Change low temp set point
Re-select the system
Low pressure alarm
LPRA
Refrigerant leak
Bad transducer
Fix leak
Replace pressure transducer
Digital Input 1
XTA1
Incorrect digital input MODE
Mechanical damage
Loose connection wire
Out of range
Correct the digital input MODE parameter
Tighten the connection wires on the controller
terminal
Replace failed sensor/switch/relay
Digital Input 2
XTA2
Incorrect digital input MODE
Mechanical damage
Loose connection wire
Out of range
Correct the digital input MODE parameter
Tighten the connection wires on the controller
terminal
Replace failed sensor/switch/relay
Digital Input 3
XTA3
Incorrect digital input MODE
Mechanical damage
Loose connection wire
Out of range
Correct the digital input MODE parameter
Tighten the connection wires on the controller
terminal
Replace failed sensor/switch/relay
Door Alarm
DROA
Door are open
Incorrect parameter
Bad door switch
Close door tightly
Declare the correct parameter relay (open/close)
Change the door switch
Communication
COMA
Loose RJ-45 coonection
Failed communication port
Replace connector
Change a new controller board