Technical data

Manual – MOVI-PLC® advanced DH.41B Controller
85
8
MOVI-PLC® advanced DHF41B control card
Technical Data and Dimension Drawings
8.3 MOVI-PLC
®
advanced DHF41B control card
The connections that are identical to those of DHE41B are described in section 8.2.
MOVI-PLC
®
advanced DHF41B control card
Part number •MOVI-PLC
®
advanced DHF41B control card: 1821 161 5
Potential levels MOVI-PLC
®
advanced DHF41B has the following potential levels:
Potential control / CAN 1 / COM1
Potential COM2
Potential binary inputs and outputs
Potential system bus CAN 2
Potential PROFIBUS
PROFIBUS connection
X30P:1 ... X30P:9
Bus terminator
Automatic baud rate
detection
Protocol options
GSD file
DP ident. number
9-pin sub D connector, pin assignment to IEC 61158
Not integrated. Connect using a suitable PROFIBUS connector with terminating resistors that can be
activated.
9.6 kBaud ... 12 MBaud
PROFIBUS DP and DP-V1 to IEC 61158
SEW_6007.GSD
Not yet assigned
DeviceNet connection
X30D:1 ... X30D:5
2-wire bus and 2-wire supply voltage DC 24 V with 5-pin Phoenix terminal
Pin assignment according to DeviceNet specification
Communication protocol Master/slave connection set acc. to DeviceNet specification version 2.0
Number of process data
words
Adjustable via DIP switches:
1 ... 10 process data words
1 ... 4 process data words with Bit-Strobe I/O
Baud rate 125, 250 or 500 kBaud; can be set using DIP switches 2
6
and 2
7
Bus cable length For thick cable according to DeviceNet specification 2.0 Appendix B
500 m at 125 kbaud
250 m at 250 kbaud
100 m at 500 kbaud
Transmission level ISO 11 98 - 24 V
MAC-ID 0 ... 63; can be set using DIP switches 2
0
... 2
5
Max. 64 stations
Supported services Polled I/O: 1 ... 10 words
Bit-Strobe I/O: 1 ... 4 words
Explicit message:
Get_Attribute_Single
Set_Attribute_Single
–Reset
Allocate_MS_Connection_Set
Release_MS_Connection_Set
P
i
f
kVA
Hz
n