Technical data
Manual – MOVI-PLC® advanced DH.41B Controller
83
8
MOVI-PLC® advanced DHE41B control card
Technical Data and Dimension Drawings
8.2 MOVI-PLC
®
advanced DHE41B control card
MOVI-PLC
®
advanced DHE41B.. control card
Part number •MOVI-PLC
®
advanced DHE41B control card: 1821 160 7
Electrical supply The following data applies to all units (MDX, MX, compact controller):
• You must supply the binary inputs and outputs separately with DC 24 V (X31:1/2).
Integrated in MOVIDRIVE
®
MDX61B:
• Power consumption: P
max
= 6.8 W
• Voltage is supplied to the MOVI-PLC
®
advanced DHE41B control card through MOVIDRIVE
®
MDX61B via the backplane connector.
• When the power supply is disconnected, the function of the control card is maintained through the
DC 24 V back up supply (external DC 24 V supply must be provided at X10:9/10 on MOVID-
RIVE
®
MDX61B.
Integrated in MOVIAXIS
®
master module (MXM):
• Power consumption: P
max
= 8.5 W
• U = DC 24 V (–15 % / +20 %)
•I
max
= 600 mA
• Voltage can be supplied to the MOVI-PLC
®
advanced DHE41B control card either by the MOVIAXIS
®
switched-mode power supply module (MXS) or by an external voltage source. To do so, connect X5
between the individual units.
• If the MOVI-PLC
®
advanced DHE41B control card is supplied with DC 24 V via the MOVIAXIS
®
switched-mode power supply module, the functionality of the MOVI-PLC
®
advanced DHE41B..
control card is maintained when the power supply is disconnected (external DC 24 V supply at X16 of
the MOVIAXIS
®
switched-mode power supply module is required).
Potential levels MOVI-PLC
®
advanced DHE41B has the following potential levels:
• Potential control / CAN 1 / COM1
• Potential COM2
• Potential binary inputs and outputs
• Potential system bus CAN 2
Memory • Program memory: 8 MByte (for user program, incl. IEC libraries)
• Data memory: 4 MByte (for IEC application)
• Retain data: 32 kByte
• System variables (retain): 8 kByte
Binary inputs
X31:3...X31:10
Internal resistance
Signal level
Isolated (optocoupler), PLC-compatible (IEC 61131-2), cycle time 1 ms, unfiltered and filtered (filter
constant ca. 2 ms)
Can be configured as binary inputs or outputs
X31:6...X31:10 are interrupt-capable (response time <100 μs)
R
i
≈ 3kΩ, I
E
≈ 10 mA
DC (+13 V...+30 V) = "1" = Contact closed (in accordance with IEC 61131)
DC (–3 V...+5 V) = "0" = Contact open (in accordance with IEC 61131)
Binary outputs
X31:3...X31:10
Signal level
PLC-compatible (IEC 61131-2), response time 1ms
Can be configured as binary inputs or outputs
Maximum permitted output current I
A_max
= DC 150 mA per binary output
All 8 binary outputs can be subject to the maximum permitted output current I
A_max
at the same time.
"0" = 0 V "1" = DC+24 V
System bus CAN 2
X32:1 ... X32:3
• System bus CAN 1 and CAN 2 to CAN specification 2.0, part A and B, transmission technology to
ISO 11898
• The CAN 2 system bus is electrically isolated
• Max. 64 stations per CAN system bus
• Max. 64 SCOM transmit objects / 32 receive objects per CAN system bus
• Address range 0...127
• Baud rate: 125 kBaud...1 MBaud
• If X32 or X33 is the bus terminator, you must connect a terminating resistor (120 Ω) externally.
• You can remove connector X32 or X33 without interrupting the system bus
• The system bus can be run in layer 2 (SCOM cyclic, acyclic) or in accordance with the SEW-
MOVILINK
®
protocol.
System bus CAN 1
X33:1 ... X33:3
Ethernet 1 System bus, reserved
Ethernet 2 • TCP/IP
• Connection options: engineering PC, other control, intranet
USB USB 1.0 to connect an engineering PC (in preparation)