Technical data

Manual – MOVI-PLC® advanced DH.41B Controller
81
7
Diagnostic procedure for PROFIBUS-DP
Error Diagnostics
7.2 Diagnostic procedure for PROFIBUS-DP
Diagnostic problem: The MOVI-PLC
®
advanced DHF41B control card
does not work on PROFIBUS.
Initial status:
The MOVI-PLC
®
advanced DHF41B control card is connected
physically to PROFIBUS.
The MOVI-PLC
®
advanced DHF41B control card is configured in the
DP master and bus communication is active.
Is the bus connector plugged in? No [A]
Yes
Response of the Profibus fault LED?
OFF
[B]
ON
[C]
FLASHES
The MOVI-PLC
®
advanced DHF41B control card detects the baud rate, but
was either not configured in the DP Master or has been configured
incorrectly.
Check whether the configured PROFIBUS address is the same as the
address set on the DIP switches.
PROFIBUS addresses identical? No [D]
Yes
You may have configured an incorrect unit type or defined the configuration
incorrectly.
Delete the configuration for the MOVI-PLC
®
advanced DHF41B control
card from the DP network.
Reconfigure the MOVI-PLC
®
advanced DHF41B control card and select
the unit designation "MOVI-PLC".
Use a predefined configuration to simplify the process. Do not change any
of the preset configuration data!
Assign the address range for your control system.
Load the configuration into the DP master and start the bus communication
again.
[A] Check the bus cabling.
[B] The MOVI-PLC
®
advanced DHF41B control card is exchanging data
cyclically with the DP master.
[C] The MOVI-PLC
®
advanced DHF41B control card cannot detect the baud
rate.
Check the bus cabling.
[D] Adapt the bus addresses.