Technical data

Manual – MOVI-PLC® advanced DH.41B Controller
79
6
Appendix
PROFIBUS-DP-V1 Functions
Error codes of
the DP-V1
services
The following table shows possible error codes of DP-V1 services that may occur in the
event of an error in the communication on DP-V1 telegram level. This table is relevant
if you want to write your own parameter assignment block based on the DP-V1 services
because the error codes are reported directly back on the telegram level.
Error_Class (from DP-
V1 specification)
Error_Class (from DP-V1
specification)
DP-V1 parameter channel
0x0 ... 0x9 hex =
reserved
0xA = application 0x0 = read error
0x1 = write error
0x2 = module failure
0x3 to 0x7 = reserved
0x8 = version conflict
0x9 = feature not supported
0xA to 0xF = user specific
0xB = access 0x0 = invalid index 0xB0 = No data block Index 47 (DB47); param-
eter requests are not supported
0x1 = write length error
0x2 = invalid slot
0x3 = type conflict
0x4 = invalid area
0x5 = state conflict 0xB5 = Access to DB 47 temporarily not
possible due to internal processing status
0x6 = access denied
0x7 = invalid range 0xB7 = Write DB 47 with error in the DB 47
header
0x8 = invalid parameter
0x9 = invalid type
0xA to 0xF = user specific
0xC = resource 0x0 = read constraint conflict
0x1 = write constraint conflict
0x2 = resource busy
0x3 = resource unavailable
0x4..0x7 = reserved
0x8..0xF = user specific
0xD...0xF = user specific
Error_Class
7 6 5 4 3 3 2 0
Error_Code
Bit:
00
I