Technical data

78
Manual – MOVI-PLC® advanced DH.41B Controller
6
Configuration of a C1 master
PROFIBUS-DP-V1 Functions
6.4 Configuration of a C1 master
The GSD file SEW-6007.GSD is also required for configuring a DP-V1 C1 master. This
file activates the DP-V1 functions of the MOVI-PLC
®
advanced DHF41B control card.
Operating mode
(DP-V1 mode)
The DP-V1 operating mode is usually when a C1 master is configured. All DP slaves
which have the DP-V1 functions enabled in their GSD file and which support DP-V1 are
operated in the DP-V1 mode. Standard DP slaves will still be run via PROFIBUS-DP.
This ensures that mixed mode is run for DP-V1 and DP-capable modules. Depending
on the specification of the master functions, a DP-V1-capable station that was
configured using the DP-V1 GSD file, can also be run in the DP operating mode.
6.5 Appendix
Sample program
for SIMATIC S7
The STEP7 code stored in the GSD file shows how parameters are accessed via the
STEP7 system function blocks SFB 52/53. You can copy the STEP7 code and import-
compile it as STEP7 source.
DP-V1 technical
data for the
DHF41B control
card
0x19 axis nonexistent Access to an axis which does not exist -
up to 0x64 Reserved - -
0x65..0xFF Manufacturer-specific - -
Error no. Meaning Used at Supplem.
information
GSD file for DP-V1: SEW-6007.GSD
Module name for configuration MOVI-PLC
Number of parallel C2 connections: 2
Supported dataset: Index 47
Supported slot number: Recommendation: 0
Manufacturer code: 10A hex (SEW-EURODRIVE)
Profile ID: 0
C2 response timeout 1s
Max. length C1 channel: 240 bytes
Max. length C2 channel: 240 bytes
00