Technical data
Manual – MOVI-PLC® advanced DH.41B Controller
77
6
Structure of the DP-V1 parameter channel
PROFIBUS-DP-V1 Functions
PROFIdrive return
codes for DP-V1
The following table shows the codes of the error number in the PROFIdrive DP-V1
parameter response according to PROFIdrive profile V3.1. This table applies if you use
the PROFIdrive services Request parameter or Change parameter.
Error no. Meaning Used at Supplem.
information
0x00 Impermissible parameter
number
Access to unavailable parameter 0
0x01 Parameter value cannot be
changed
Change access to a parameter value
that cannot be changed
Subindex
0x02 Low or high limit exceeded Change access with value outside the
value limits
Subindex
0x03 Faulty subindex Access to unavailable subindex Subindex
0x04 No array Access with subindex to non-indexed
parameter
0
0x05 Incorrect data type Change access with value that does not
match the data type of the parameter
0
0x06 Setting not permitted (can
only be reset)
Change access with value unequal to 0
where this is not permitted
Subindex
0x07 Description element cannot
be changed
Change access to a description element
that cannot be changed
Subindex
0x08 Reserved (PROFIdrive Profile V2: PPO-Write
requested in IR not available)
-
0x09 No description data avail-
able
Access to unavailable description
(parameter value is available)
0
0x0A Reserved (PROFIdrive Profile V2: Access group
wrong)
-
0x0B No operation priority Change access without rights to change
parameters
0
0x0C Reserved (PROFIdrive Profile V2: wrong
password)
-
0x0D Reserved (PROFIdrive Profile V2: Text cannot be
read in cyclic data transfer)
-
0x0E Reserved (PROFIdrive Profile V2: Name cannot be
read in cyclic data transfer)
-
0x0F No text array available Access to text array that is not available
(parameter value is available)
0
0x10 Reserved (PROFIdrive Profile V2: No PPO-Write)
0x11 Request cannot be exe-
cuted because of operating
state
Access is temporarily not possible for
reasons that are not specified in detail
0
0x12 Reserved (PROFIdrive Profile V2: other error)
0x13 Reserved (PROFIdrive Profile V2: Data cannot be
read in cyclic interchange)
0x14 Value impermissible Change access with a value that is within
the value limits but is not permissible for
other long-term reasons (parameter with
defined single values)
Subindex
0x15 Response too long The length of the current response
exceeds the maximum transmittable
length
0
0x16 Parameter address imper-
missible
Illegal value or value which is not sup-
ported for the attribute, number of
elements, parameter number or
subindex or a combination
0
0x17 Illegal format Write request: Illegal format or format of
the parameter data which is not
supported
0
0x18 Number of values is not
consistent
Write request: Number of parameter data
values that do not match the number of
elements in the parameter address
0
00
I