Technical data

Manual – MOVI-PLC® advanced DH.41B Controller
67
6
Structure of the DP-V1 parameter channel
PROFIBUS-DP-V1 Functions
Parameter set-
ting procedure
via dataset 47
Parameter access takes place with the combination of the DP-V1 services write and
read. The master transfers the parameter setting job to the slave by sending Write.req.
followed by slave-internal processing.
The master now sends a Read.req to request the parameter setting response. The
master repeats the Read.req if the Read.res from the slave is negative. As soon as
parameter processing in the MOVI-PLC
®
advanced DHF41B control card (slave) is
completed, the control card answers with a positive response Read.res. The user data
now contains the parameter setting response of the parameter setting request that was
previously sent with Write.req ( following figure). This telegram sequence applies to
both a C1 and a C2 master.
61587AXX
Write.req DS47Parameter
Parameter
Parameter
Parameter
Parameter
Read.req DS47
Read.req DS47
Write.res
Read.res(-)
Read.res(+)
with data (parameter request)Request
Response
Response
Request
Processing
without data
without data
without data
without data
with data (parameter response)
Master PROFIBUS-DP-V1 Slave (DHF41B)
00
I