6
Features of the SEW DP-V1 interfaces
PROFIBUS-DP-V1 Functions
6.2 Features of the SEW DP-V1 interfaces
The SEW fieldbus interfaces to PROFIBUS DP-V1 have the same communication
features as the DP-V1 interface. The MOVI-PLC
®
advanced DHF41B control card is
controlled via a C1 master with cyclical process data in accordance with the DP-V1
standard. This C1 master (usually a PLC) can also use an 8-byte MOVILINK
®
parameter
channel during cyclical data exchange to execute the parameter services with the
MOVI-PLC
®
advanced DHF41B control card. The read and write services allow the C1
master access to connected stations via the DP-V1 C1 channel.
Parallel to these two parameter channels, a further two C2 channels can be set up. For
example, the first C2 master (visualization) could use these channels to read parameter
data, and a second C2 master (notebook) could use them to configure the MOVI-PLC
®
advanced DHF41B control card using the MOVITOOLS
®
software.
58379AXX
Figure 13: Parameter channels for PROFIBUS DP-V1
Cyclic IN/Out
Process Data
MOVI-PLC
DP
Parameterbuffer
Parameterbuffer
cyclic
SEW PROFIBUS
DP-V1 Interface
C1-Parameterbuffer
C2-Parameterbuffer
C2-Parameterbuffer
Acyclic DP1-V1
C1-Services
DP:
C1-Master C2-Master C2-Master
Acyclic DP1-V1
C2-Services
PROFIBUS DP-V1
Acyclic DP1-V1
C2-Services
PD
R
DP: 8 Byte Param.
00
I