Technical data

Manual – MOVI-PLC® advanced DH.41B Controller
63
6
Introduction to PROFIBUS-DP-V1
PROFIBUS-DP-V1 Functions
The PROFIBUS-DP-V1 network differentiates between various master classes.
Class 1 master
(C1 master)
The C1 master performs the cyclical data exchange with the slaves. Typical C1 masters
include control systems, such as PLCs, which exchange cyclical process data with the
slave. If the DP-V1 function has been activated via the GSD file, the acyclical connection
between C1 master and slave is established automatically when the cyclical connection
of the PROFIBUS-DP is being established. Only one C1 master can be operated in a
PROFIBUS DP-V1 network.
Class 2 master
(C1 master)
The C2 master itself does not perform cyclical data exchange with the slaves. Examples
of a typical C2 master are visualization systems or temporarily installed programming
devices (Notebook / PC). The C2 master uses exclusively acyclic connections for
communication with the slaves. The acyclic connections between C2 master and slave
are established by the Initiate service. The connection is established once the Initiate
service has been performed successfully. An established connection enables cyclical
data exchange with the slaves using Read or Write services. Several C2 masters can
be active in a DP-V1 network. The number of C2 connections, established simulta-
neously for a slave, is determined by the slave. The MOVI-PLC
®
advanced DHF41B
control card supports two parallel C2 connections.
Datasets (DS) User data transported via a DP-V1 service is collected in datasets. Each dataset is
identified uniquely by its length, a slot number and an index. The structure of dataset 47
is used for DP-V1 communication with the MOVI-PLC
®
advanced DHF41B control card.
This dataset is defined as the DP-V1 parameter channel for drives as of V3.1 in the
PROFIdrive profile drive engineering of the PROFIBUS Nutzerorganisation (user
group). Different procedures for accessing parameter data in the MOVI-PLC
®
advanced
DHF41B control card are provided via this parameter channel.
DP-V1 services The DP-V1 expansions offer new services, which can be used for acyclical data
exchange between master and slave.
The system distinguishes between the following services:
DP-V1 Alarm han-
dling
In addition to the acyclical services, the DP-V1 specification also defines extended
alarm handling. The PROFIBUS-DP-V1 system differentiates between various alarm
types. As a result, unit-specific diagnostics cannot be evaluated in DP-V1 operation via
the 'DDLM_SlaveDiag' DP-V1 service. DP-V1 alarm handling has not been defined for
drive engineering.
C1 master Connection type: MSAC1 (master/slave acyclical C1)
Read Read dataset
Write Write dataset
C2 master Connection type: MSAC2 (master/slave acyclical C2)
INITIATE Establish C2 connection
ABORT Disconnect C2 connection
Read Read dataset
Write Write dataset