Special cases
Operating Characteristics on PROFIBUS-DP
Incorrect service
code in the param-
eter channel
An incorrect code was specified for the management byte or reserved byte during
parameter setting via the parameter channel. The following table shows the return code
for this special case.
Troubleshooting:
Check bits 0 and 1 in the parameter channel.
Incorrect length
specification in
parameter channel
A data length other than 4 data bytes was specified in a read or write service during
parameter setting via the parameter channel. The following table displays the return
codes.
Troubleshooting:
Check bit 4 and bit 5 for the data length in management byte 0 of the parameter channel.
Both bits must be set to "1".
Internal communi-
cation error
The return code listed in the following table is sent back if an internal communication
error has occurred. The parameter service transferred via the fieldbus may not have
been performed and should be repeated. If this error persists, switch the MOVI-PLC
®
advanced DHF41B control card off and on again. In this way, the control card is
reinitialized.
Troubleshooting:
Repeat the read or write service. If this error occurs again, disconnect the MOVI-PLC
®
advanced DHF41B control card from the power source and switch the system on again.
If the error persists, consult SEW Service.
Code (dec) Meaning
Error class: 5 Service
Error code: 5 Illegal parameter
Add. code high: 0 -
Add. code low: 0 -
Code (dec) Meaning
Error class: 6 Access
Error code: 8 Type conflict
Add. code high: 0 -
Add. code low: 0 -
Code (dec) Meaning
Error class: 6 Access
Error code: 2 Hardware fault
Add. code high: 0 -
Add. code low: 0 -