Technical data

60
Manual – MOVI-PLC® advanced DH.41B Controller
5
Special cases
Operating Characteristics on PROFIBUS-DP
Additional code The Additional code contains SEW-specific return codes for errors in the parameter
settings for MOVI-PLC
®
advanced DHF41B. These codes are returned to the master
under Error class 8 = Other error. The following table shows all possible codes for the
Additional code.
5.5 Special cases
Special return
codes
Errors in parameter settings, which cannot be identified either automatically by the
application layer of the fieldbus system or by the system software of the MOVI-PLC
®
advanced DHF41B control card, are treated as special cases. The following errors can
occur depending on the control card used:
Incorrect coding of a service via parameter channel
Incorrect length specification of a service via parameter channel
Internal communication error
Add. code
high (hex)
Add. code low
(hex)
Meaning
00 00 No error
00 10 Illegal parameter index
00 11 Function / parameter not implemented
00 12 Read access only
00 13 Parameter lock is active
00 14 Factory setting is active
00 15 Value for parameter too large
00 16 Value for parameter too small
00 17 Reserved
00 18 Error in system software
00 19 Reserved
00 1A Parameter access only via RS485 interface
00 1B Parameter is access-protected
00 1C Reserved
00 1D Invalid value for parameter
00 1E Factory setting was activated
00 1F Reserved
00 20 Reserved