Technical data
Manual – MOVI-PLC® advanced DH.41B Controller
57
5
Parameter setting via PROFIBUS-DP
Operating Characteristics on PROFIBUS-DP
The MOVI-PLC
®
advanced DHF41B control card now processes the read service and
sends the service confirmation back by changing the handshake bit.
The above table shows how a read service is coded in management byte 0. The data
length is irrelevant, only the service identifier for the read service must be entered. This
service is now activated in the MOVI-PLC
®
advanced DHF41B control card when the
handshake bit changes. For example, it would be possible to activate the read service
with the management byte coding 01hex or 41hex.
Writing a
parameter via
PROFIBUS-DP
Due to the cyclical transfer of the parameter channel, to execute a write service via the
8-byte MOVILINK
®
parameter channel, the handshake bit may only be changed if the
complete parameter channel has been set up for the specific service. Observe the
following sequence when writing a parameter:
1. Enter the index of the parameter to be written in byte 2 (Index high) and byte 3 (Index
low).
2. Enter the data to be written in bytes 4...7.
3. Enter the service identifier and the data length for the write service in the manage-
ment byte (byte 0).
4. Transfer the write service to the MOVI-PLC
®
advanced DHF41B control card by
changing the handshake bit.
The MOVI-PLC
®
advanced DHF41B control card now processes the write service and
returns the service confirmation by changing the handshake bit.
7 / MSB 6 5 4 3 2 1 0 / LSB
00/1
1)
1) Bit value is changed
X
2)
2) Not relevant
X
2)
0001
Service identifier
0001 = Read parameter
Data length
Not relevant for Read service
Handshake bit
Must be changed on every new task in cyclical transmission.
Status bit
0 = No error during execution of service
1 = Error during execution of service
00