Technical data
Manual – MOVI-PLC® advanced DH.41B Controller
49
4
Configuration for a PROFIBUS DP master
Configuration and Startup
The following figure shows the configuration data structure defined in IEC 61158. This
configuration data is transferred to the MOVI-PLC
®
advanced DHF41B control card
when the DP master is started.
Data integrity Integral data is data that always has to be transmitted between the higher-level control-
ler and the MOVI-PLC
®
advanced DHF41B control card as one block and must never
be transmitted separately.
Data integrity is particularly important for transmitting position values or complete posi-
tioning tasks. The reason that data integrity is so important is that data which is not
transmitted integrally could come from different program cycles of the higher-level
controller, which would lead to undefined values being transmitted to MOVI-PLC
®
advanced DHF41B controller.
For PROFIBUS DP, data communication between the higher-level control and the
MOVI-PLC
®
advanced DHF41B control card is carried out with the setting "Data
integrity over entire length".
7 / MSB 6 5 4 3 2 1 0 / LSB
Data length
0000 = 1 byte/wort
1111 = 16 bytes/words
Input/output
00 = Special identifier formats
01 = Input
10 = Output
11 = Input/output
Format
0 = Byte structure
1 = Word structure
Integrity over
0 = Byte or word
1 = Entire length
Note:
The MOVI-PLC
®
advanced DHF41B control card does not support the "Special identifier
formats" coding! Only use the setting "Integrity over entire length" for data transmission.
00
I