Technical data
Manual – MOVI-PLC® advanced DH.41B Controller
47
4
Configuration for a PROFIBUS DP master
Configuration and Startup
The following tables contain additional information on possible DP configurations.
• The "Parameter data/Process data configuration" column displays the name of the
configuration. These names also appear in a selection list in the configuration
software for the DP master.
• The "DP configurations" column shows the configuration data that is sent to the
MOVI-PLC
®
advanced DHF41B control card when the link to the PROFIBUS DP
system is being established.
Slot 1:
Slot 2:
Slot 3:
Parameter data
configuration
Meaning / notes DP configuration
Empty Reserved 0x00
Parameter data
configuration
Meaning / notes DP configuration
Empty Reserved 0x00
Param (4words) MOVILINK
®
parameter channel
configured
0xC0, 0x87, 0x87
Process Data
configuration
Meaning / notes DP configuration
1 PD Process data exchange via
1 process data word
0xC0, 0xC0, 0xC0
2 PD Process data exchange via
2 process data words
0xC0, 0xC1, 0xC1
3 PD Process data exchange via
3 process data words
0xC0, 0xC2, 0xC2
4 PD Process data exchange via
4 process data words
0xC0, 0xC3, 0xC3
5 PD Process data exchange via
5 process data words
0xC0, 0xC4, 0xC4
6 PD Process data exchange via
6 process data words
0xC0, 0xC5, 0xC5
7 PD Process data exchange via
7 process data words
0xC0, 0xC6, 0xC6
8 PD Process data exchange via
8 process data words
0xC0, 0xC7, 0xC7
9 PD Process data exchange via
9 process data words
0xC0, 0xC8, 0xC8
10 PD Process data exchange via
10 process data words
0xC0, 0xC9, 0xC9
11 PD Process data exchange via
11 process data words
0xC0, 0xCA, 0xCA
12 PD Process data exchange via
12 process data words
0xC0, 0xC7, 0xC7
13 PD Process data exchange via
13 process data words
0xC0, 0xCC, 0xCC
14 PD Process data exchange via
14 process data words
0xC0, 0xCD, 0xCD
15 PD Process data exchange via
15 process data words
0xC0, 0xCE, 0xCE
00
I