Technical data
Manual – MOVI-PLC® advanced DH.41B Controller
29
3
Installation option DH.41B in MOVIDRIVE® MDX61B
Assembly / Installation Notes
Fault Profibus
LED (L17)
The Fault Profibus LED indicates that communication via the PROFIBUS interface is
working properly.
Run Profibus LED
(L18)
The Run Profibus LED indicates the proper functioning of the PROFIBUS electronics
(hardware).
3.5 Installation option DH.41B in MOVIDRIVE
®
MDX61B
3.6 Installing the option DH.41B in the MOVIAXIS
®
master module
BUS FAULT Diagnostics Remedy
Off • The MOVI-PLC
®
advanced DHF41B
control card exchanges data with the
PROFIBUS-DP master (data exchange
status).
-
Red • Connection to the DP master has failed.
• The MOVI-PLC
®
advanced DHF41B
control card cannot detect the PROFIBUS
baud rate.
• Bus interruption has occurred.
• PROFIBUS-DP master not in operation.
• Check the PROFIBUS connection on
the unit.
• Check the configuration of the
PROFIBUS DP master.
• Check all the cables in the
PROFIBUS network.
Flashing red
(1 Hz)
• The MOVI-PLC
®
advanced DHF41B con-
trol card detects the baud rate. However,
the DP-Master does not address the
MOVI-PLC
®
advanced DHF41B control
card.
• The MOVI-PLC
®
advanced DHF41B con-
trol card was either not configured in the
DP Master or has been configured
incorrectly.
• Check and correct the PROFIBUS
station address set on the
MOVI-PLC
®
advanced DHF41B
control card and in the configuration
software of the DP master.
• Check and correct the configuration
of the DP master.
• Use the GSD file SEW_6007.GSD
with the designation MOVI-PLC for
configuration.
RUN Profibus Diagnostics Remedy
Green • PROFIBUS hardware OK. -
Flashing
green
(1 Hz)
• The PROFIBUS station address set on
the DIP switches is more than 125. When
the PROFIBUS station address is set to a
value higher than 125, the MOVI-PLC
®
advanced DHF41B control card uses
PROFIBUS station address 4.
1. Check and correct the PROFIBUS
station address on the DIP switches.
2. Switch on all drive inverters again.
The modified PROFIBUS address
will only take effect after a restart.
The MOVI-PLC
®
advanced DH.41B control card is installed as specified in section 3.4.
Voltage is supplied to MOVI-PLC
®
advanced DH.41B via MOVIDRIVE
®
MDX61B. A
separate voltage supply is only required for the binary inputs and outputs (terminal X31).
The MOVI-PLC
®
advanced DH.41B control card is installed as specified in section 3.4.
To wire the system bus, connect terminal X33 (CAN1) or X32 (CAN2) on MOVI-PLC
®
advanced DH.41B to terminal X9 (signaling bus of the MOVIAXIS
®
supply module or a
MOVIAXIS
®
axis module) or to terminal X12 (CAN2 bus of a MOVIAXIS
®
axis module).
The MOVIAXIS
®
master module provides additional connections that are described in
the following section.