Technical data
Manual – MOVI-PLC® advanced DH.41B Controller
25
3
Installing the MOVI-PLC® advanced DHF41B control card
Assembly / Installation Notes
The MOVI-PLC
®
advanced DHF41B control card supports the address range 0...125.
Any change made to the PROFIBUS station address during operation does not take
effect immediately. You must restart the drive inverter with the MOVI-PLC
®
advanced
DHF41B control card for the changes to take effect (power + 24 V off/on).
3.4.3 Connecting DeviceNet (terminal X30D)
Connection to the DeviceNet fieldbus system is in preparation.
Pin assignment The assignment of the connecting terminals is described in the DeviceNet specification
(Volume I, Appendix A).
The DHF41B option card is opto-decoupled on the driver side in accordance with the
DeviceNet specification (Volume I, Chapter 9). This means the CAN bus driver must be
powered with 24 V voltage via the bus cable. The DeviceNet specification (Volume I,
Appendix A) also explains which cable you should use. The connection must be made
according to the color code specified in the following table.
61492AXX
The default setting for the PROFIBUS station address is 4:
2
0
→ Significance: 1 × 0 = 0
2
1
→ Significance: 2 × 0 = 0
2
2
→ Significance: 4 × 1 = 4
2
3
→ Significance: 8 × 0 = 0
2
4
→ Significance: 16 × 0 = 0
2
5
→ Significance: 32 × 0 = 0
2
6
→ Significance: 64 × 0 = 0
DHF41B
L18L17
X30P
61612AXX
Pin no. Signal Meaning Color coding
1V– 0V24 BK
2CAN_L CAN_L BU
3 DRAIN DRAIN blank
4CAN_H CAN_H WH
5V+ 24 V RD
DFD11B
1
2
3
4
5
DHF41B
X30D