Technical data

Manual – MOVI-PLC® advanced DH.41B Controller
23
3
Installing the MOVI-PLC® advanced DHF41B control card
Assembly / Installation Notes
For PROFIBUS operation:
DIP switches
for setting
the PROFIBUS
station address
For operation via
DeviceNet:
DIP switches for setting
the MAC ID and the baud
rate
2
0
2
1
2
2
2
3
2
4
2
5
2
6
2
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
Significance: 1
Significance: 2
Significance: 4
Significance: 8
Significance: 16
Significance: 32
Significance: 64
The MAC-ID (Media Access Control Identi-
fier) is set using DIP switches 2
0
... 2
5
. The
MAC-ID represents the node address
(address range 0 ... 63)
Setting the baud rate
Setting the baud rate
Terminal X38:
SafetyBus
(plug-in terminals)
X38:1
X38:2
X38:3
Reserved
Reserved
Reserved
Terminal X31:
Binary inputs and outputs
(plug-in terminals)
X31:1
X31:2
X31:3
X31:4
X31:5
X31:6
X31:7
X31:8
X31:9
X31:10
+24 V input
REF24V
DIO 0
DIO 1
DIO 2
DIO 3
DIO 4
DIO 5
DIO 6
DIO 7
Voltage input DC+24 V
Reference potential for binary signals
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Terminal X34:
RS485 interface COM1,
COM2
(plug-in terminals)
X34:1
X34:2
X34:3
X34:4
X34:5
X34:6
RS+
RS+ isolated
RS–
RS– isolated
DGND
GND isolated
Signal RS485+
Signal RS485+ isolated
Signal RS485–
Signal RS485– isolated
Reference potential
Reference potential
Terminal X35:
USB connection (in
preparation)
X35:1
X35:2
X35:3
X35:4
USB+5 V
USB–
USB+
DGND
DC 5 V voltage supply
Signal USB–
Signal USB+
Reference potential
Terminal X36:
Ethernet 1 connection
System bus (RJ45 socket)
X36
Standard Ethernet assignment
Terminal X37:
Ethernet 2 connection
(RJ45 socket)
X37
Terminal X32:
System bus CAN 2
(electrically isolated)
(plug-in terminals)
X32:1
X32:2
X32:3
REF_CAN 2
CAN 2H
CAN 2L
Reference potential for system bus CAN 2
System bus CAN 2 high
System bus CAN 2 low
Terminal X33:
System bus CAN 1
(plug-in terminals)
X33:1
X33:2
X33:3
DGND
CAN 1H
CAN 1L
Reference potential for system bus CAN 1
System bus CAN 1 high
System bus CAN 1 low
DIP switch S1
Default IP address
S1 Default IP address
Ethernet 2 connection
DIP switch S2
Changeover PROFIBUS /
DeviceNet
S2 PROFIBUS
DeviceNet
Reset button T1 T1 Reset
The connections that are identical to those of DHE41B are described in section 3.3.
Front view
of the MOVI-PLC
®
advanced DHF41B
control card
Designation
LED
DIP switches
Terminal
Function