Technical data
Manual – MOVI-PLC® advanced DH.41B Controller
21
3
Installing the MOVI-PLC® advanced DHE41B control card
Assembly / Installation Notes
24V / I/O OK LED
(L10)
The 24V / I/O OK LED indicates the status of the voltage supply for binary inputs /
outputs.
3.3.9 DIP switch S1 default IP address
You can use the DIP switch S1 to set a fixed IP address for the Ethernet 2 connection.
This IP address will become effective when the system is restarted.
24V / I/O OK Diagnostics Remedy
Green • Voltage supply for the binary inputs and
outputs is OK.
-
Off • Voltage supply is not applied at the binary
inputs and outputs.
1. Switch off the drive inverter in
which the MOVI-PLC
®
advanced
DHE41B control card is installed.
2. Check and correct the cabling of
the binary inputs and outputs in
accordance with the electrical wir-
ing diagram.
3. Check the current consumption of
the connected actuators (max.
current → Sec. 8).
4. Switch on the drive inverter in
which the MOVI-PLC
®
advanced
DHE41B control card is installed.
Orange Voltage supply for the binary inputs and out-
puts is applied. However, one of the following
faults has occurred:
• Overload on one or more binary inputs or
outputs
• Overtemperature of the output driver
• Short circuit in at least one of the binary
inputs or outputs
S1 switch position Meaning
Top Fixed IP address 192.168.10.5
Bottom Address entered in the configuration file (→ Sec. 4.1)