Technical data

Manual – MOVI-PLC® advanced DH.41B Controller
21
3
Installing the MOVI-PLC® advanced DHE41B control card
Assembly / Installation Notes
24V / I/O OK LED
(L10)
The 24V / I/O OK LED indicates the status of the voltage supply for binary inputs /
outputs.
3.3.9 DIP switch S1 default IP address
You can use the DIP switch S1 to set a fixed IP address for the Ethernet 2 connection.
This IP address will become effective when the system is restarted.
24V / I/O OK Diagnostics Remedy
Green Voltage supply for the binary inputs and
outputs is OK.
-
Off Voltage supply is not applied at the binary
inputs and outputs.
1. Switch off the drive inverter in
which the MOVI-PLC
®
advanced
DHE41B control card is installed.
2. Check and correct the cabling of
the binary inputs and outputs in
accordance with the electrical wir-
ing diagram.
3. Check the current consumption of
the connected actuators (max.
current Sec. 8).
4. Switch on the drive inverter in
which the MOVI-PLC
®
advanced
DHE41B control card is installed.
Orange Voltage supply for the binary inputs and out-
puts is applied. However, one of the following
faults has occurred:
Overload on one or more binary inputs or
outputs
Overtemperature of the output driver
Short circuit in at least one of the binary
inputs or outputs
S1 switch position Meaning
Top Fixed IP address 192.168.10.5
Bottom Address entered in the configuration file ( Sec. 4.1)