Technical data

Manual – MOVI-PLC® advanced DH.41B Controller
17
3
Installing the MOVI-PLC® advanced DHE41B control card
Assembly / Installation Notes
Wiring diagram for CAN 2 system bus
Cable specification Use a 4-core twisted and shielded copper cable (data transmission cable with
braided copper shield). Clamping without conductor end sleeves is possible in accor-
dance with IEC 60999. The cable must meet the following specifications:
Core cross section 0.25 ... 1.0 mm
2
(AWG 23 ... AWG 18)
Line resistance 120 Ω at 1 MHz
Capacitance per unit length 40 pF/m at 1 kHz
Suitable cables include CAN bus or DeviceNet cables.
Cable length The permitted total cable length depends on the baud rate setting of the system bus:
125 kbaud 320 m
250 kbaud 160 m
500 kBaud 80 m
1000 kbaud 40 m
Terminating
resistor
Switch on the system bus terminating resistor at the start and end of the CAN system
bus connection (MOVIDRIVE
®
B, DIP switch S12 = ON; MOVITRAC
®
B, DIP switch
S1 = ON). Switch off the terminating resistors on all other units (MOVIDRIVE
®
B, DIP
switch S12 = OFF; MOVITRAC
®
B, DIP switch S1 = OFF). If, for example, the
MOVI-PLC
®
advanced DH.41B control card is at the end of the CAN 2 system bus,
connect a terminating resistor with 120 Ω between pin X32:2 and pin X32:3 (with
CAN 1: terminating resistor between X33:2 and pin X33:3).
60526AXX
Figure 4: CAN 2 system bus connection using the example of MOVIDRIVE
®
MDX60B/61B / MOVITRAC
®
B drive inverters
MDX61B
DGND
MDX60B/61B
X12
SC11
2
1
3
SC12
DHE41B
X31X32X33
1
2
3
1
2
3
1
2
3
2
3
1
SC11
DGND
ON OFF
S12
X12:
2
1
SC12
3
ON OFF
S12
X45
X46
1
23456HL
FSC11B
MOVITRAC
®
B
S1
OFF
ON
7
S2
X44
There should not be any potential displacement between the units connected via
the CAN 2 system bus.
There must not be any potential displacement between the units connected via the
CAN 1 system bus.
Take suitable measures to avoid potential displacement, such as connecting the unit
ground connectors using a separate cable.