Technical data

14
Manual – MOVI-PLC® advanced DH.41B Controller
3
Installing the MOVI-PLC® advanced DHE41B control card
Assembly / Installation Notes
3.3 Installing the MOVI-PLC
®
advanced DHE41B control card
3.3.1 Functional description of the terminals, DIP switches and LED
Front view
of the MOVI-PLC
®
advanced DHE41B
control card
Designation
LED
DIP switches
Terminal
Function
60108AXX
LED LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED10
CAN 1 status
CAN 2 status
IEC progr. status
PLC status
User LED
DIO6/7
DIO4/5
DIO2/3
DIO0/1
24 V / I/O OK
Status of CAN 1 system bus
Status of CAN 2 system bus
Status of control program
Status of control firmware
User-programmable
Status of input or output DIO 6/7
Status of input or output DIO 4/5
Status of input or output DIO 2/3
Status of input or output DIO 0/1
Status of voltage supply I/O
Terminal X31:
Binary inputs and outputs
(plug-in terminals)
X31:1
X31:2
X31:3
X31:4
X31:5
X31:6
X31:7
X31:8
X31:9
X31:10
+24 V input
REF24V
DIO 0
DIO 1
DIO 2
DIO 3
DIO 4
DIO 5
DIO 6
DIO 7
Voltage input DC+24 V
Reference potential for binary signals
Binary input or output (DIO 0)
Binary input or output (DIO 1)
Binary input or output (DIO 2)
Binary input or output (DIO 3)
Binary input or output (DIO 4)
Binary input or output (DIO 5)
Binary input or output (DIO 6)
Binary input or output (DIO 7)
Terminal X34:
RS485 interface COM1, COM2
(plug-in terminals)
X34:1
X34:2
X34:3
X34:4
X34:5
X34:6
RS+
RS+ isolated
RS–
RS– isolated
DGND
GND isolated
Signal RS485+
Signal RS485+ isolated
Signal RS485–
Signal RS485– isolated
Reference potential
Reference potential
Terminal X35:
USB connection
(In preparation)
X35:1
X35:2
X35:3
X35:4
USB+5 V
USB–
USB+
DGND
DC 5 V voltage supply
Signal USB–
Signal USB+
Reference potential
Terminal X36:
Ethernet 1 connection
System bus (RJ45 socket)
X36
Standard Ethernet assignment
Terminal X37:
Ethernet 2 connection
(RJ45 socket)
X37
Terminal X32:
System bus CAN 2
(electrically isolated)
(plug-in terminals)
X32:1
X32:2
X32:3
REF_CAN 2
CAN 2H
CAN 2L
Reference potential for system bus
CAN 2
System bus CAN 2 high
System bus CAN 2 low
Terminal X33:
System bus CAN 1
(plug-in terminals)
X33:1
X33:2
X33:3
DGND
CAN 1H
CAN 1L
Reference potential for system bus
CAN 1
System bus CAN 1 high
System bus CAN 1 low
DIP switches
Default IP address
S1 Default IP address
Ethernet 2 connection
X35
X36
X37
2
4
6
1
3
5
X34
DHE41B
1
2
3
1
3
4
2
1
2
3
1
2
3
1
2
3
X32X33
2
4
6
1
3
5
8
10
7
9
X31
T1
S1
L1 L2 L3 L5XM L6 L7 L8 L9L4 L10