Technical information

IDENTIFICATION
The BG warm air heater can be identified by the Technical Plate that shows the main technical and performance data.
It if gets damaged or lost, you should ask for a copy to the Assistance Technical Service.
MANUFACTURER
IDENTIFICATION
WARM AIR HEATER
Model
Serial Nr
Country PIN Code
Category Code
Type Year
Nominal heat rating kW
Thermal power delivered kW
Air flow-rate (+20°C) m
3
/h
Electrical supply
Maximum electric power taken kW
Maximum current taken A
Electric protection grade
Fuel used: oil
TECHNICAL DATA
Type 1 2 3 4 5 6 7
Total heat rating kW 46,8 71,1 93,0 104,6 190,0 258,8 391,0
kcal/h
40.300 61.200 80.000 90.000 163.400 222.600 336.250
Heat delivered kW 42,2 64,4 83,9 94,2 168,2 230,3 347,6
kcal/h
36.300 55.400 72.100 81.090 144.600 198100 298.950
Efficiency % 90,1 90,5 90,1 90,1 88,5 89 88,9
Pressure of the Combustion
chamber
Pa 18 20 25 8 2 39 32
Combustion chamber
volume
dm
3
48,8 77,4 129,5 228,5 490,0 640,0 1050,0
Net smoke temperature °C 200 220 220 220 249 248 227
Consumption
- Oil
(4)
kg/h 3,95 6,00 7,84 8,82 16,0 21,8 32,9
Device type B23
Airflow +20°C
Nm
3
/
h
2.800 4.500 5.300 6.300 11.500 15.300 23.000
DT
°K 43 41 45 45 43 45 45
Thermostat settings
°C 25-35-100
Operation temperature
°C -5/+40
Electrical supply
230V 50Hz ~ 400V 3N 50Hz ~
Engine rating kW 0,25 0,59 0,73 0,73 2,20 3,00 4,00
Maximum absorbed current
A 2,6 6,7 7,6 7,6 5,1 7,0 9,1
Electric protection degree IP 20
(1) Refers to conditions: 1013 mbar, 15°C, P.C.I. 8570 kcal/m3
(2) Refers to conditions: 1013 mbar, 15°C, P.C.I. 11070 kcal/kg – 5635 kcal/l
(3) Refers to conditions: 1013 mbar, 15°C, P.C.I. 10905 kcal/kg – 6285 kcal/l
(4) Refers to conditions: 1013 mbar, 15°C, P.C.I. 10200 kcal/kg
NOTE: On request, the heaters can be arranged differently to satisfy special efficiency requirements.
8
All Parts available from
www.sparesgiant.com
01772 329 565