Technical information
2
TROUBLE SHOOTING
ANOMALY
CAUSE
REMEDIES
THE GENERATOR DOES NOT WORK
EITHER IN VENTILATION OR IN
HEATING
No energy supply
Check electric connections
Check the line and auxiliary load fuses
THE GENERATOR DOES NOT WORK
IN SUMMER VENTILATION
No energy supply to the fan motor
Check electric connections
Check line and auxiliary load fuses
Check for actuation of the motor thermal
cut-out (only for three-phase versions)
THE GENERATOR DOES NOT HEAT
No energy supply to the oil burner
Check electric connections
Check the line and auxiliary fuses
Check that the room thermostat contact is
closed
Check for actuation of the motor thermal
cut-out (only for three-phase versions)
Check for actuation of the LIMIT thermostat
THE BURNER FLAME IGNITES BUT
GOES OUT AFTER A FEW SECONDS
Electric connection not correctly m
ade
Check supply polarity
(phase + neutral + earth)
Burner to be checked or faulty
Check burner settings
Replace the electronic burner control device
Check and / or replace the flame detector
electrode
THE OIL BURNER FLAME IGNITES
BUT GOES OUT AFTER A FEW
SECONDS
Electrical connection not made
correctly
Check supply polarity
(phase + neutral + earth)
Burner to be checked or faulty
Check burner settings
Replace the electronic burner control device
Check and/or replace the Burner photocell
27
All Parts available from
www.sparesgiant.com
01772 329 565