IMPORTANT NOTES:
GFCI WIRING INSTRUCTIONS
FOR INSTALLATION OF A (2) TWO-POLE GFCI-CIRCUIT BREAKER INTO A LOAD CENTER. THESE ASSEMBLIES ARE DESIGNED
ESPECIALLY FOR USE BY QUALIFIED ELECTRICIANS TO MEET THE SWIMMING POOL & SPA REQUIREMENTS OF ARTICLES 680-
12 & 680-42 OF THE 1996 NATIONAL ELECTRICAL CODE (NEC) 680-12. DISCONNECTING MEANS SHALL BE ACCESSIBLE, LO-
CATED WITHIN SIGHT OF POOL, SPA EQUIPMENT, AND SHALL BE LOCATED AT LEAST (5) FIVE FEET HORIZONTALLY FROM
INSIDE WALLS OF THE POOL, SPA OR HOT TUB. NATIONAL ELECTRIC CODE (NEC) 682-42. PROTECTION OF AN OUTLET THAT
SUPPLIES A SELF CONTAINED SPA OR HOT TUB EQUIPMENT ASSEMBLY, ALL SPA EQUIPTMENT SHALL BE PROTECTED BY A
(GFCI) GROUND-FAULT CIRCUIT INTERRUPTER. TO ENSURE THAT PEOPLE THAT ARE IN THE SPA ARE PROTECTED.
INSTALLATION OF THE GFCI CIRCUIT BREAKER, INCLUDING AMP SIZING AND SELECTION OF CONDUCTOR SIZE & TYPE, MUST
BE INSTALLED BY A QUALIFIED ELECTRICIAN, IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC), OWNERS
MANUAL, AND ALL FEDERAL, STATE AND LOCAL CODES AND REGULATIONS IN EFFECT AT THE TIME OF INSTALLATION.
A
LOAD NEUTRAL CONNECTION IS REQUIRED, BECAUSE SPAS CONTAIN BOTH 115 AND 240 VOLT EQUIPMENT.
THE
GFCI LINE NEUTRAL WIRE (PIGTAIL) MUST BE CONECTED IN ALL INSTALLATIONS. THE GFCI WILL NOT OPERATE CORRECTLY
WITHOUT CONNECTION OF LINE NEUTRAL WIRE TO AN INCOMING LINE NEUTRAL.
HOUSE BREAKER BOX
SPA LOAD BOX
WIRING DIAGRAM (240
VAC)
FOR LICENSED ELECTRICIAN ONLY
NOTE: USE COPPER CONDUCTORS ONLY
Input From Power
Pole Transformer
Neutral
(Ground Bar)
WARNING:
THIS
WIRING MUST BE DONE BY A LICENSED ELECTRICIAN.
HOT HOT
IF
THE SPA IS
WIRED INCORRECTLY;
YOUR
WARRANTY IS
VOID!!!
A B
BREAKER
BREAKER
GRN (Ground)
Black (Hot)
30/50 Amp, 60 Hz GFCI Breaker (2 Hots, 1 Neutral, 1 Ground)
Ground Bar
Terminal Block
4
BREAKER
BREAKER
Red (Hot)
White (Neutral)
GRN (Ground)
Red (Hot)
Red
3
Wht
2
Red
Red
White
Black
To spa circuit
board (see
configuration
Blk
1
Black (Hot)
Black
options below)
Spa Cabinet
Electrical Box
Insulated Power Cord (2 Hots, 1 Neutral, 1 Ground)
GFCI SUB PANEL
Wht (Neutral)
Red
(Hot)
.
Blk
(Hot)
GRN (Ground)
Ground Bar
White (Neutal) From
Load Neutral
Red
(Hot)
Blk
(Hot)
GRN (Ground)
CAUTION!
Use #6 AWG
Copper Wire
Only.
Insulated Power Cord
(2 Hots, 1 Neutral, 1 Ground)
White (Neutral) From Line
Neutral (GFCI Pigtail)
CIRCUIT BOARD CONFIGURATION OPTIONS
This spa is factory configured for a 240
VAC 50 amp service. In this
JP2
JP2
configuration, the heater
will operate
while both jet pumps are running.
An alternate 30 amp service can be configured for locations where 50
amp service is unavailable. In this configuration, the heater
will not
operate
while either jet pumps are running.
To configure spa for 30
1
2
3
4
5
6
7
8
Factory
50 Amp @
1
2
3
4
5
6
7
8
Alternate
30 Amp @
Place
Jumper
amp service, place a jumper across the circuit board's JP2 jumper
position #8 as shown (right).
240 VAC
Service
Configuration
Here!
240 VAC
Service
Configuration
NOTE: THE SKILLS AND TOOLS NECESSARY FOR THE SAFE REPAIR OF THIS
SPA REQUIRE THE SERVICES OF AN AUTHORIZED SERVICE TECHNICIAN.
Product specifications are subject to change without notice.
Use the installation instructions supplied with this product.
22